Manual
FLT
®
Series FlexSwitch
TM
OPERATION
Fluid Components International LLC 21
Jumper
J32 J12 J13 J14 J33
FLT93-F ELEMENT WATTAGE
(560 OHM HTR)
0.57
WATTS
0.52
WATTS
0.49
WATTS
0.20
WATTS
OFF
FLT93-S ELEMENT WATTAGE
(110 OHM HTR)
3
WATTS
1.75
WATTS
0.75
WATTS
0.27
WATTS
OFF
Table 3-3A Selectable Heater Wattage Control
J13 is standard for FLT93-S and J14 is standard for FLT93-F
Jumper
J13 J14 J33
FLT93-F ELEMENT WATTAGE
(560 OHM HTR)
N.A.
0.20
WATTS
OFF
FLT93-S ELEMENT WATTAGE
(110 OHM HTR)
0.75
WATTS
N.A. OFF
Table 3-3B Fixed Heater Wattage Control
FLOW/LEVEL TEMP
ALARM NO. 1 J20 J21
ALARM NO. 2
J18 J19
Table 3-4 Application
Jumper ALARM NO. 1
J27 RELAY DE-ENERGIZED WITH LOW FLOW, LOW LEVEL
(DRY) OR HIGH TEMPERATURE.
J26 RELAY DE-ENERGIZED WITH HIGH FLOW, HIGH LEVEL
(WET) OR LOW TEMPERATURE.
Jumper ALARM NO. 2
J25 RELAY DE-ENERGIZED WITH LOW FLOW, LOW LEVEL
(DRY) OR HIGH TEMPERATURE.
J24 RELAY DE-ENERGIZED WITH HIGH FLOW, HIGH LEVEL
(WET) OR LOW TEMPERATURE.
Table 3-5 Relay Energization
J23 DUAL SPDT (ONE RELAY PER ALARM)
J22 SINGLE DPDT (DISABLES ALARM NO. 2)
Table 3-6 Relay Contact Confi guration