13.9.1 Status output active state
The status output can be compared to an electrical relay that can function as make or break contact. For
safety-relevant applications, the operator will choose the break contact setting so that a power failure or
failure of the electronics can be detected like an alarm. In standard applications, the output is used as
make contact.
The
Status output state active state function allows the operator to define the behavior of the status out-
put.
Status output active
[closed]
As mentioned in Section 12.4.3.1 Selection window/make a selection, the operator can choose between
the following settings:
¾ closed
¾ open
13.9.2 Status output 1 assignment
This function allows the operator to define to which event the status output is to be assigned. The most
general assignment is the alarm assignment because all set limiting values and the self-test function are
then monitored via the status output.
After selecting the
Status output assignment function, press to display the current assignment.
Output 1 assigned to
[Alarm]
As mentioned in Section 12.4.3.1 Selection window/make a selection, the operator can choose between
the following settings:
¾ Flow direction recognition
o Forward flow
o Reverse flow
¾ Limiting values:
o MIN QM
o MAX QM
o MIN density
o MAX density
¾ All limiting values and error detection
o Alarm
¾ Pulse output 2 for custody transfer operations
o IMP2 90°,
When selecting the IMP2 90° setting, a second pulse output will be realized via the status output that can
be used for custody transfer operations.