Designation Terminal designation Type of protection Standard
EEx ia EEx e (Not Ex)
Signal outputs
11 and 12 x x Current 1, 0/4 to 20mA
with HART
®
41 and 42 x
13 and 14 x x Current 2, 0/4 to 20mA
43 and 44 x
16 and 17 x x Binary output 1
(passive pulse)
46 and 47 x
45 and 48 x Binary output 1
(active pulse)
15 and 18 x
19 and 20 x x Binary output 2
(status or second pas-
sive pulse output for
custody transfer opera-
tions)
49 and 50 x
33 and 34 x x Option
Binary output 3
(status output during
custody transfer opera-
tions)
53 and 54 x
Profibus PA option
39 (A) and 40 (B) x
Control unit BE
Shield, -, + x x
Alternatives for cur-
rent output 2
21 and 22 x x Binary input
51 and 52 x
Modbus/Profibus DP
with RS 485-IS
35 (A) and 36 (B)
(not currently available)
x x
Profibus DP 37 (A) and 38 (B)
(not currently available)
x
¾ Since the signal outputs cannot be activated simultaneously owing to the limited number of ter-
minals available, one of the aforementioned options must be selected.
Field bus devices
(Profibus PA) are not outfitted with an analog or impulse output.
¾ A maximum of 8 signal output terminals is available (in addition to the terminal for the control unit
and Profibus PA).
¾ “Increased safety” type of protection signal outputs are to be connected only to "Extra low volt-
age" degree of protection circuits with safe electrical isolation in accordance with DIN VDE 0100
part 410.
¾ Under no circumstances are “Increased safety” signal outputs to be combined with “In-
trinsic safety” signal outputs
.
¾ If interface output RS 485 (under development and not currently available), which is only avail-
able in an “Increased safety” model, is selected, all signal outputs must also have this type of pro-
tection.
¾ If “Control input” or “RS 485 interface” are selected, current output 2 is not supplied.
¾ If the sensor and transmitter are interconnected using a cable, the following cable is to be used:
SLI2Y (SP) CY 5 x 2 x 0.5 mm (for explosion-proof applications, grey for non-explosion
proof applications).
CMU & CT OPERATING MANUAL
Part No 06EN003380 rev 1.6
Page 45 of 112