Error Error text #Comment Outputs Input
No. Remedy text status status
1 I1 - Power on
OK Power on has activated. Active Active
2 I2 - Add-on Module
Applied A new module has been added to the system. Active Active
3 I3 - Add-on Module An add-on module is bad or has been removed.
Install This can also be an internal add-on module. Active Active
4 I4 - Param. corrected A less vital parameter in the converter has been
OK replaced by its default value. Active Active
20 W20 - Totalizer 1 During initialization, the check of the saved totalize
Reset manually value failed. The saved totalizer value is not reliable.
Reset the totalizer value manually to rely on readings. Active Active
20 W20 - Totalizer 2 During initialization, the check of the saved totalize
Reset manually value failed. The saved totalizer value is not reliable.
Reset the totalizer value manually to rely on readings. Active Active
21 W21 - Pulse overflow Actual flow is too big compared with pulse width and Reduced
Adjust pulse settings mass/pulse. pulse width Active
22 W22 - Batch timeout Duration of batching has exceeded a predefined Batch out-
Check installation maximum time. put on zero Active
23 W23 - Batch overrun Batch quantity has exceeded a predefined maximum Batch out-
Check installation overrun mass or volume. put on zero Active
24 W24 - Batch neg. flow
Check flow direction Negative flow direction during batch. Active Active
30 W30 - Flowsaturated
Adjust max. flow Flow is above Q
max.
settings. Max. 120 % Active
31 W31- Empty pipe Pipe is empty. Zero Active
32 W32 - Temp. to high The temperature of the fluid has exceeded the max.
Adjust temperature temperature rating of the sensor (180 °C). Active Active
33 W33 - Temp. to low The temperature of the fluid has exceeded the min.
Adjust temperature temperature rating of the sensor (-50 °C). Active Active
34 W34 - Zero Adj. fail Zero-point values are out of limits because of flow in the
Check flow = zero sensor. Check zero flow conditions, valves, pumps etc. Active Active
35 W35 - Current Out 1 Current output exceeds 120%. Ensure that the sensor is
Check max. settings correctly sized and check maximum flow setting. Active Active
36 W36 - Freq/Pulse Out1 Freq/Pulse output exceeds 120%. Ensure that the sensor
Check max. settings is correctly sized and check maximum flow setting. Active Active
40 P40 - SENSORPROM
â
Insert SENSORPROM
â
unit not installed. Active Active
41 P41 - Parameter range A parameter is out of range.
Switch off and on The error will disappear at the next power-on. Active Active
42 P42 - Current output Current loop is disconnected or the loop resistance
Check cables is too big. Active Active
43 P43 - Internal error Internal error.
Switch off and on Active Active
49 P49 - Protec. viol. Too many errors occured at the same time.
Switch off and on Some errors are not detected correctly. Active Active
50 P50 - Temp. cable Error in temperature sensor, check cables and
Check cable connectors. Active Active
51 P51 - Pick-up 1 Pick-up 1 amplitude too low. Check cables or application
Check cable/install. for damping (air/gas in liquid). Active Active
52 P52 - Pick-up 2 Pick-up 2 amplitude too low. Check cables or application
Check cable/install. for damping (air/gas in liquid). Active Active
60 F60 - CAN comm. error CAN bus communication error. An add-on module, the
Converter/add-on module display module or the converter is defect Zero Inactive
61 F61 - SENSORPROM
â
err. SENSORPROM
â
data is not reliable.
Replace Active Active
62 F62 - SENSORPROM
â
ID SENSORPROM
â
unit ID doesn't match instrument ID.
Replace The SENSORPROM
â
unit is from another instrument. Zero Inactive
63 F63 - SENSORPROM
â
It is not possible to read from the SENSORPROM
â
Replace unit . Active Active
70 F70 - Pick-up phase Check cables/polarity. Active Active
71 F71 - Driver phase Check cables/polarity. Active Active
80-83 F80, 81, 82, 83 - Internal error Restart or replace. Active Active
84 F84 - Sensor level Pick-up amplitude saturated. Active Active
97 F97 - Add-on module to old Replace. Active Active
Error code level: W = Warning F = Fatal P = Permanent
ERROR
CODES