INSTALLATION StepSeven
The EchoSwitch® should always be mounted perpendicular to the liquid surface and installed using the
provided Viton® mounting gasket.Make sure that the fitting and transmitter threads are not damaged or
worn.Always hand‐tighten the transmitter within the fitting.Perform an installed leak test under normal
process conditions prior to system start up.Note: The preferred mounting fitting for the LU77 Series is the
LM52‐1400(2”threadx1”thread)reducerbushing.
MountingGuide
1. Donotmountatanangle.
2. Liquidshouldneverenterthedeadband.
3. SideWall:
a. Mountatleast3”fromthesidewall.
b. ForLU77Series‐mountatleast2”fromthe side
wall.
4. Donotmountwhereobstacleswillintrudeintosensor’s
beamwidth.
a. BeamWidth:3”(7.6cm)diameter[2”(5cm)for
LU77series].
5. Donotmountinavacuum.
6. Avoidmountinginthecenterofadometoptank.
7. Inconebottomtank,positionthesensoroverthe
deepestpartofthetank.
Installationinexistingfittings:Iftheexistingfittingislarger
than the threads of the EchoSwitch®, select a reducer
bushing such as the LM52‐1400 (2” thread x 1” thread) or
LM52‐2400(3”threadx2”thread).
LM52‐1400
LM52‐2400
Donotinstallat
anglerelativeto
theliquid.
Donotinstall
within2”oftank
sidewall.
(3”forDL34series)
Donotinstallwith
objectsinthe
beam.
Donotinstallin
applicationswith
vacuum.
Metal Tanks (LU77 Series Only):Flowline ultrasonic sensors have been optimized for use in non‐metallic
fittings.
1. Forbestperformance,avoidtheuseofmetallicfittings.
a. Useaplastic2”x1”reducerbushing,suchastheLM52‐1400oraplastic1”flange,suchasthe
LM52‐1850formetallictanks.
2. While installations directly into a 1” metal fitting are not recommended, acceptable results may be
obtained if the 1” fitting is a half coupling in form and the outer diameter of the coupling is tightly
wrappedinvinyltapetodampenvibration.