User guide
RevA MN300282 19of34
CONFIGURATION(cont.) StepFive
HowtoDuplextworelays:DuplexenablesEchoSwitch®tousetworelaystoalternateaftereachcyclewhile
performingalead‐lagoperation.Tobegin,configure tworelaysinthesame mode(ex:two relaysare setas
PUMPsthatFILLortworelayssetasPUMPsthatEMPTY).BesuretosetonerelaywithanONSetPointatthe
PrimaryLevelandtheotherrelayONSetPointattheBackupLevel.SettingtherelayswiththesameONlevel
willhavecausebothrelaystoturnonatthesame time.Oncethisiscompleted,seethestepsbelow.Example
belowshowstworelays(AandB)usedtoAutoEmptyatank:
1. Make sure at least two relays are in the same
modeforpumps.
a. If this is not true, then M‐PLEX will not
appear.
2. InTOP‐LEVELMENUmode,selectM‐PLEX.
3. SelectDUPLEX.
a. If three relays are configured in the same
mode,continuetostep4.
b. If only two relays are configured, jump to
step5.
4. Select R1_R2 (Relay 1 & 2), R2_R3 (Relay 2 & 3)
orR1_R3(Relay1&3).
a. EchoSwitch® will allow you to select two of
threerelaystoduplex.
5. SelectEXITtoreturntoTOP‐LEVELMENU.