Owner's manual

27 AUG 08 PRELIMINARY MANUAL 39 of 57
Rev 1_3 Commander LI90 Series
General (Open Functions)
o Opening Screen indicates the Level of Liquid in the tank/vessel along with the
true analog (4-20 mA) input
Regardless on how the input level is configured, the bar graph will show
the true 4-20 mA input provided by the sensor
o Pressing the Lower Left Soft key will jump the display to indicate the relay status.
Above the relay status will be the liquid level.
Pressing the lower left soft key will return the display back to the opening
screen
Pressing the upper left soft key will jump the screen to the HAND / OFF /
AUTO (H.O.A.) functions for each relay.
o The H.O.A. screen for each relay will indicate each relay, the current status of
each relay and soft keys to jump back or to the next relay
AUTO – This mode places the relay in automatic. Relay will energize
based upon the ON setting and will De-energize based upon the OFF
setting.
OFF – This mode turns the relay OFF (de-energized). The ON and OFF
settings are ignored in this mode. This mode is helpful in taking a relay
off-line for maintenance.
HAND – This mode turns the relay ON (energized). This mode is helpful
in overriding a relay function. Relay will be energized until
The OFF is selected or
When the AUTO mode is selected and the level drops below the
OFF setting