Instruction Manual

DataView™ LI55 Level Controller Instruction Manual
93 | Page
Reset Meter to Factory Defaults
When the parameters have been changed in a way that is difficult to
determine what’s happening, it might be better to start the setup
process from the factory defaults.
Instructions to load factory defaults:
1. Press and hold MENU for 5 seconds to access the Full Menu
2. From Setup, press and hold MENU for 3 seconds to access the
Advanced Features Menu
3. Press Up button to go to
Diagnostics menu
4. Press and hold Right button for three seconds, press
Enter when display flashes
reset.
Note: If Enter is not pressed within three seconds, the display
returns to the
Diagnostics menu.
5. The meter goes through an initialization sequence (similar as on
power-up), and loads the factory default settings.
Note: The dual-scale selection for some level applications (d-SCAL) is
not reset to the single scale factory default. This can be changed
using the Setup – Input menu.
ENTER
to accept
RIGHTUP