F4 Operation
A digital input, F4, is standard on the meter. This digital input is
programmed identically to function keys F1, F2, and F3. The input is
triggered with a contact closure to COM, or with an active low signal.
During operation, F4 operates according to the way it has been
programmed in the
Advanced Features – User menu.
Maximum/Minimum Readings
The max & min readings (peak & valley) reached by the process can be
displayed either continuously or momentary:
1. Display briefly by assigning to the RIGHT, UP, or ENTER
buttons or to the digital input in the
User menu.
2. Display continuously by assigning either display to max/min
through the
Display menu.
Any of the RIGHT, UP, or ENTER buttons or the digital input can be
programmed to reset the max & min readings. The meters are set at the
factory to display the max reading by pressing the Up button and to use
the Right button to access the
Reset menu.
To display max reading using function key with factory defaults:
1. Press Up button to display maximum reading since the last
reset/power-up.
2. To reset max/min press Right button to access the Reset menu.
The max & min displays are reset to actual values.
3. Press Menu to exit max/min display reading.
To display max/min readings continuously:
Assign either display to Max (d Hi), Min (d Lo), or toggle between Max
and Min (
d HL) every 10 seconds.