METER OPERATION
The meter is capable of accepting current (0-20 mA, 4-20 mA) and
voltage signals (0-5 V, 1-5 V, 0-10 V,
10 V) and displaying these
signals in engineering units from -99999 to 999999 (
e.g. a 4-20 mA
signal could be displayed as -50.000 to 50.000).
The dual-line display can be customized by the user to operate in such
a way as to satisfy a specific application. Typically the main display is
used for the process variable; while the second display is used for
engineering units, custom legend, or set point indication.
The analog input can be scaled to display the process in two different
scales; for example: with
d-SCAL enabled, the main display could
indicate level in feet and the second display could indicate the volume in
gallons.
Front Panel Buttons Operation
Button
Symbol
Description
Press to enter or exit Programming Mode,
view settings, or exit max/min readings
Press to reset max/min readings or other
parameter/function assigned through the
User
menu
Press to display max/min readings or other
parameter/function assigned through the
User
menu
Press to acknowledge relays or other
parameters/function assigned through the
User menu
Function Keys Operation
During operation, the programmable function keys operate according to
the way they have been programmed in the
Advanced Features – User
menu.
The table above shows the factory default settings for RIGHT, UP, and
ENTER.