Meter Copy or Cloning Instructions
!
Caution!
Do not connect the two meters to
the same signal source while
cloning. Internal calibration may
be affected.
1. Connect two meters using a LI56-1000 meter copy cable.
Warning!
Using standard CAT5 or other cable will cause
damage to both meters. Use LI56-1000 meter copy
cable only.
2. Do not connect the two meters to the same signal source.
3. Power up both meters. Leave Clone meter in Run Mode.
4. Enter the
Advanced Features menu of the Master meter; see
Advanced Features Menu on page 75.
5. Scroll to the
Copy function using the Up button then press
Enter.
6. The meter displays the message
Send. Press Enter, the display
flashes while sending data. The message
done is displayed when
copying is completed.
7. The Clone meter displays the message CPY rC while being
programmed then the message
done when copying is completed.
The meter initializes and returns to Run Mode using the same
settings as the Master.
8. If meter to be cloned does not respond to the data being sent, refer
to
Copy Function Requirements above.
ENTERENTER