Instruction Manual
DataView™ LI55 Level Controller Instruction Manual
52 | Page
Setting the Relay Operation (relay)
This menu is used to set up the operation of the relays.
1. Relay action [Available on full main menu only]
a. Automatic reset only (non-latching) [default]
b. Automatic + manual reset at any time (non-latching)
c. Latching (manual reset only)
d. Latching with Clear (manual reset only after alarm
condition has cleared)
e. Pump alternation control (automatic reset only)
f. Sampling (the relay is activated for a user-specified time)
g. Off (relay state controlled by Interlock feature)
2. Set point
3. Reset point
4. Fail-safe operation [Available on full main menu only]
a. On (enabled)
b. Off (disabled)
5. Time delay [Available on full main menu only]
a. On delay (0-999.9 seconds)
b. Off delay (0-999.9 seconds)
6. Relay action for loss (break) of 4-20 mA input (ignore, on, off)
[Available on full main menu only]
!
Caution!
During setup, the relays do not follow the input and they
will remain in the state found prior to entering the Relay
menu.