Instruction Manual
DataView™ LI55 Level Controller Instruction Manual
36 | Page
Setting the Relay Operation (
relay)
To set the relay's setpoints and reset points see Programming Set and
Reset Points on page 54.
Relay
Setup
rly 1
relay
Relay 2-4
00300.0
set 1
set 1
rly 1
rst 1
rly 1
00200.0
rst 1
ENTER
ENTER ENTER
ENTER
ENTER ENTER
Scaling the 4-20 mA Analog Output (
Aout)
The 4-20 mA analog output can be scaled to provide a 4-20 mA signal
for any display range selected.
No equipment is needed to scale the analog output; simply program the
display values to the corresponding mA output signal.
The Analog Output menu is used to program the 4-20 mA output based
on display values.
Enter the Empty value for when the input is 4 mA. Enter the Full value
for when the input is 20 mA.
aout
Setup
empty
aout
00000.0
Empty
full
aout
To
Password
Menu
02000.0
Full
Press ENTER
to Save
ENTER
ENTER ENTER ENTER
Setting Up the Password (
pass)
To set up the password see page 73 for details.
Note: The Main menu allows for setup of only one password (
Pass 1).