Instruction Manual

DataView™ LI55 Level Controller Instruction Manual
35 | Page
Setting the Units (
units)
Select units from list or enter a custom tag to be shown on the lower
display. Press the Up button to scroll through the unit choices. Press
Enter to accept unit choice.
For custom units press the Up button to scroll through characters. Press
the Right button to move to the next segment. Up to six characters may
be configured for units. Press Enter to accept settings.
units
Setup
Gal
units
liter
units
Inch
units
cm
units
feet
units
meter
units
cust
units
percnt
units
ENTER
UP UP UP
UP
UP UP UP
UP
Setting the Decimal Point (
dEc pt)
To set the decimal point see page 44 for details.
Scaling the Meter (
SCALE)
The process input (4-20 mA, 10 VDC) can be scaled to display the
process variable in engineering units.
A signal source is not needed to scale the meter; simply program the
inputs and corresponding display values.
Enter the Empty value for when the input is 4 mA. Enter the Full value
for when the input is 20 mA.
SCALE
Setup
empty
scale
00000.0
Empty
full
scale
To Relay
Menu
02000.0
Full
Press ENTER
to Save
ENTER
ENTER ENTER ENTER