Instruction Manual

DataView™ LI55 Level Controller Instruction Manual
11 | Page
Relays
RATING 2 or 4 SPDT (Form C) internal and/or 4 SPST (Form A)
external; rated 3 A @ 30 VDC and 125/250 VAC resistive
load; 1/14 HP ( 50 W) @ 125/250 VAC for inductive loads
NOISE
SUPPRESSION
Noise suppression is recommended for each relay contact
switching inductive loads; see page 23 for details.
DEADBAND 0-100% of span, user programmable
HIGH OR LOW
ALARM
User may program any alarm for high or low trip point.
Unused alarm LEDs and relays may be disabled (turn off).
RELAY
OPERATION
Automatic (non-latching) and/or manual reset
Latching (requires manual acknowledge) with/without clear
Pump alternation control (2 to 8 relays)
Sampling (based on time)
Off (disable unused relays and enable Interlock feature)
Manual on/off control mode
RELAY RESET User selectable via front panel buttons
1. Automatic reset only (non-latching), when the input
passes the reset point.
2. Automatic + manual reset at any time (non-latching)
3. Manual reset only, at any time (latching)
4. Manual reset only after alarm condition has cleared
(latching)
Note: Front panel button or digital input may be assigned to
acknowledge relays programmed for manual reset.
TIME DELAY 0 to 999.9 seconds, on & off relay time delays
Programmable and independent for each relay
FAIL-SAFE
OPERATION
Programmable and independent for each relay.
Note: Relay coil is energized in non-alarm condition.
In case of power failure, relay will go to alarm state.
AUTO
INITIALIZATION
When power is applied to the meter, relays will reflect the
state of the input to the meter.