Instruction Manual

RevA MN204260 15of16
TROUBLESHOOTING StepNine
DisplayDescriptors:Thefollowingarethedisplay’soperationaldescriptors,meaningandcorrectiveaction:
WARMUP
WARMUPisseenwhenpowerisfirstappliedtotheEchoPod®andPodView®.WARMUP
indicatesthatthedisplayiswaitingfortheEchoPod®toacquireandsendavalidlevel
reading.
MENU Indicatesthemenuforconfigurationofrelaysetpoints.
PUMP PUMPistheidentifierfortherelaysetpointsaffectingPumporValveoperations.
OFF OFFistherelaysetpointthatturnsOFFthepump.
ON ONistherelaysetpointthatturnsONthepump.
LAG LAGisthesetpointthatturnsONthelagpump.
ALARM AlarmistheidentifierfortherelaysetpointsaffectingAlarmoperations.
HIGH# HIGH#istherelaysetpointthatenergizesahighalarmrelay.
LOW# LOW#istherelaysetpointthatenergizesalowalarmrelay.
CHECKWIRES
NotAllfourwiresareproperlyconnectedtotheEchoPod®.Checkthewiringbetweenthe
PodView®andtheEchoPod®.
UPDATEFWREV
TheattachedEchoPod®isnotrunningaversionofthe firmware(50.0orhigher)thatis
compatiblewithPodView®.ConnecttheEchoPod®toWebCal®6.0andupdatethe
firmware.
