Instruction Manual
RevA MN204260 13of16
GETTINGAROUNDPODVIEW® StepEight
ChangingaPumpSetPoint:EchoPod®sensormodelswithrelayshave(1‐4)channels.Ifafteraccessingthe
MENU,PUMPappearsinthe display,thenatleast(1)relayisconfiguredforpumporvalvecontrol.Simplex
pump control has (1) ON and (1) OFF setting.Duplex pump control (2‐pumps) has a third additional LAG
setting.Note:Priortomakinganychanges,werecommendthatyouwritedownallexistingsetpointvalues.
Theexamplebelow highlights a duplex pump systemin an automatic emptyor automaticfilloperation with
(1)LAG,(1)ONand(1)OFFsetpoint.Usethefollowingstepstochangeyour simplexorduplexpumpcontrol
settings.
AutomaticEmptyOperation
AutomaticFillOperation
StepstoChangePumpSet Points
1. HoldSELECTfor5secondstoentertheMENU.
2. PressSELECTwhenPUMPappears.
3. PressSELECTwhenthesetpoint(ON,OFF,LAG)youwantto
changeappears.
4. PresstheUPandDOWNbuttonstoincreaseordecreasethe
setpointtothedesiredvalue.Toscrollfaster,holdSELECT
whilepressingUPorDOWN.
5. Toenterthesetpoint,holdSELECTfor2seconds.
6. Tochangeanothersetpoint,press
SELECTwhentheset
pointappears.
7. ToexittheMENU,pressSELECTwhenRUNappears.
TechTips
Neverplacearelaysetpoint(ON,OFF,LAG)attheliquidemptyorliquidfullposition.Youshouldhave
atleastsomedistanceorvolumebufferseparatingthem.Forexample,
ina500gallontank,therelay
setpointscouldbeplacedat≥10gallonsor≤490gallons.