WIRING WIRING
Models LU10-___5 Only:
The LU10-___5 level switch has been approved for use in Class I,
Groups A, B, C & D; UNDER CERTIFICATE NUMBER LR 79326-
4. DO NOT USE THE LZ12, LP15, LP10 or LO10 SERIES IN
INTRINSICALLY SAFE APPLICATIONS. The Entity parameter for
the LU10-___5 are:
Vmax = 32 VDC
Imax = 0.5 A
Ci = 0 µF
Li = 0 mH
Intrinsically Safe Control Drawing:
Wiring to a Flowline Controller:
LC90 Series Controller
4 or 20 mA Signal Output
Red Wire
Black Wire
Shield
HAZARDOUS LOCATION
Class I, Groups A, B, C & D
Class II, Groups E, F & G
Class III
NON-HAZARDOUS LOCATION
Sensor Drawing: LSD1
Rev. B 10-01-02
Sensor Models
LU10
Entity Parameters
V
max = 32V
I
max = 0.5A
C
i 0
L
i 0
Associated
Equipement
(see notes 1 and 4)
Notes:
1. CSA certified associated equipment with entity parameters.
2. Vmax Voc, Imax Isc, Ci + C cable ʺ Ca., Li + L cable ʺ La.
3. Installation should be in accordance with CEC Part I, or
NFPA 70.
4. Associated equipment must be installed per manufacturers
instructions
STANDARD
CONTROLLER
RELAY 1 RELAY 2
POWER
INPUT 1 INPUT 2A INPUT 2B
-
+
-
+
INVERT
DELAY
INVERT
DELAY
LATCH
ON
OFF
Black
Red
Non-Hazardous Area Hazardous Area
Voc = 17.47 VDC
Isc = 0.4597 A
Ca = 0.494 µF
La = 0.119 µH
Vmax = 32 VDC
Imax = 0.5 A
Ci = 0 µF
Li = 0 µH
Models LU10-___5 Only:
The LU10-___5 level switch has been approved for use in Class I,
Division 1, Groups A, B, C & D; EEx ib IIC T6;
UNDER CERTIFICATE NUMBER LCIE 01.E6048X. DO NOT
USE THE LZ12, LP15, LP10 or LO10 SERIES IN INTRINSICALLY
SAFE APPLICATIONS. The Entity parameter for the LU10-___5
are:
North America Europe
Vmax = 32 VDC Ui = 32 VDC
Imax = 0.5 A Ii = 0.5 A
Pmax = 1.3 W Pi = 1.3 W
Ci = 0 µF Ci = 0 µF
Li = 0 µH Li = 0 µH
Intrinsically Safe Control Drawing:
Red Wire
Black Wire
Shield
HAZARDOUS LOCATION
Class I, Division1,
Groups A,B,C,D
EEx ib IIC T6
NON-HAZARDOUS LOCATION
Sensor Drawing: U10900
Sheet 1 of 2
Rev. B 4-02-01
Sensor Models
LU10-___5
Entity Parameters:
North America
V
max
= 32V
I
max = 300 mA
P
max = 1.3 W
C
i = 0 µF
L
i = 0 µH
Europe
U
i = 32V
I
i = 300 mA
P
i = 1.3 W
C
i = 0 µF
L
i = 0 µH
Associated
Equipment
Entity Parameters:
North America
V
oc ≤ Vmax
Isc ≤ Imax
Ca ≥ Ci +Ccable
La ≥ Li +Lcable
Europe
U
o ≤ Ui
Io ≤ Ii
Co ≥ Ci +Ccable
Lo ≥ Li +Lcable
Red Wire
Black Wire
Shield
HAZARDOUS LOCATION
Class I, Division1,
Groups A,B,C,D
EEx ib IIC T6
NON-HAZARDOUS LOCATION
Sensor Drawing: U10900
Sheet 2 of 2
Rev. B 4-02-01
Sensor Models
LU10-___5
Entity Parameters for 12-32 Lines:
Vmax = 32V, Ui = 32V
I
max = 300 mA, Ii = 300 mA
P
max = 1.3 W, Pi = 1.3 W
C
i = 0 µF, Ci = 0 µF
L
i = 0 µH, Li = 0 µH
Entity Parameters for Switch Outputs:
Vmax = 32V, Ui = 32V
I
max = 500 mA, Ii = 500 mA
P
max = 1.3 W, Pi = 1.3 W
C
i = 0 µF, Ci = 0 µF
L
i = 0 µH, Li = 0 µH
Associated Equipment
Entity Parameters for 12-32 Lines:
Voc ≤ Vmax, Uo ≤ Ui
Isc ≤ Imax, Io ≤ Ii
Ca ≥ Ci +Ccable, Co ≥ Ci +Ccable
La ≥ Li +Lcable, Lo ≥ Li +Lcable
Entity Parameters for Switch Outputs:
Voc ≤ Vmax, Uo ≤ Ui
Isc ≤ Imax, Io ≤ Ii
Ca ≥ Ci +Ccable, Co ≥ Ci +Ccable
La ≥ Li +Lcable, Lo ≥ Li +Lcable
Green Wire
White Wire
Notes: PARAMETERS DEPEND ON OUTPUT TYPE
1. Installation should be in accordance with CEC Part 1, or NFPA 70.
2. Associated Equipment shall be CSA certified with entity parameters
connected in accordance with manufacturers instructions.