Manual
4of16 MN301035 RevB
DIMENSIONS StepThree
Technology:A sealed pressure transmitter is placed near or on the bottom of the tank.A stainless steel
pressure diaphragm within the pressure transmitter is exposed on one side to the application liquid.The
othersideisexposedtothereferencepressureviaasmallventilationtubelocatedinsideofthePolyurethane
cable.A difference in pressure between liquid and reference pressures will slightly deflect the diaphragm.
The deflection of the diaphragm is measured by a built‐in microprocessor that provides greater linearity
correctionovercommonthermalcompensationmethods.A4‐20mAcurrentsignalproportionaltheheightof
theliquidisgeneratedfromthemicroprocessor.
LD34Series
LD35Series
MaterialCompatibility
o TheLD34/LD35seriesismadeof316StainlessSteel(316SS)withacableofPolyurethaneorEthylene
Tetrafluoroethylene(ETFE).TheLD35serieshasaPTFEcoatedFKMfluoroelastomerface.
o Makesurethattheswitchiscompatiblewiththeapplicationliquids.Todeterminethechemical
compatibilitybetweenthesensoranditsapplicationliquids,refertotheCompassCorrosionGuide,
availablefromCompassPublications(858‐589‐9636).
Optional Desiccant Filter (LD90‐3000):For extra protection against humidity we offer the LD90‐3000
desiccantfilterthatcan
beattachedtotheventtube.