GETTINGSTARTED(continued) StepSix
Howtoconfigureapanelmeterwhenapressuretransmitterisused?
This method works with the LI55 series, LI25 Series, LI10 Series and LI50 Series.These panel meters are
configured using the SCALE function.The SCALE function typically has four settings.These settings are as
follows:
Settings Default Represents TypicalSetting
Input1 04.000 Inputcurrent@Empty 04.000(mA)
Display1(Empty) 04.000 Displayvalue@Empty Emptyvalue
Input2 20.000 Inputcurrent@Full 20.000
Display2(Full) 20.000 Displayvalue@Full FullValue(mA)
Remember, pressure transmitters are configured so 0 psi = 4 mA and the maximum psi = 20 mA.Most
pressure transmitter applications will not use the full range of the transmitter and requires you to
proportionallyscalethecurrentoutputofthepressuretransmitter.Therefore,afulltankwilltypicallyhavea
currentlessthan20mA.Thegoalinconfiguringthepanelmeteristocalculatethecurrentwhenthetankis
full.Todothis,usethefollowingformula:
(FullTankHeight/MaximumLiquidHeight)x16+4=CurrentatFull
Example:A40foottankwithaSG=0.9willhaveamaximumpressureof15.58psi.A20psisensorisselected
foruse.TheMaximumLiquidHeight =(20psix2.31’/psi) /0.9=51.33feet.Usingtheaboveformula,the
CurrentatFull=[(40feet/51.33feet)x16+4]=16.468mA.
TheCurrentatFullwillbeusedastheInput2value.Thismeansthatwhenthedisplayreadsacurrentequal
toCurrentatFull,itwilldisplaytheFullvalue(Display2value).Thepanelmeterwillbeconfiguredasfollows:
Settings Configured
Input1 04.000
Display1 Empty
Input2 16.468
Display2 Full
Note:ThevaluesforemptyandfullrepresentwhatthedisplaywillshowwhenthetankiseitherEmptyorFull.
EmptyandFullmustbethesameunits(example:Gallons,Inches,percent).
ThedefaultfortheInput1is4mAandtypicallywillneverbechanged.
Typically,
theEmptysettingwillbewhatisinthetankwhenitisempty(example:000.0Gallons,000.0
inches,000.0feetetc.).
TheFullsettingwillbewhatisinthetankwhenitisfull(example:500.0Gallons,120.0inches,10.0
feet,etc.).