ELECTRICALINSTALLATION StepEight
WireLength‐Themaximumlengthofwireconnectingthetransmitterandreceiverisafunctionofwiresizeand
receiver resistance.Wiring should not contribute more than 10% of the receiver resistance to total loop
resistance.Forextremelylongruns(ov er 1000 feet),choosereceiverswithhigherresistancetominimizethesize
andcostofconnectingleads. Wherewiringlengthisunder100feet,wireassmallas22AWGcanbeused.
Wiring ‐ An external power supply delivering 1028 VDC with minimum current capability of 40 mA DC (per
transmitter)isrequiredtopowerthecontrolloop.SeeFig.Aforconnectionofthepowersupply,transmitter
andreceiver.Therangeofappropriatereceiverloadresistance(RL)fortheDC powersupplyvoltageavailable
isexpressedbytheformula:
RLmax=(Vsup10V)/20mADC
Shieldedcableisrecommendedforcontrolloopwiring.
UsetheRedwireasthe(+)andtheBlackwireasthe().
Fig.A
WiringControlDrawing
