Instruction Manual

RevB MN301030 11of14
ELECTRICALINSTALLATION StepSeven
Wiring:An external power supply delivering 1330 VDC with minimum current capability of 40 mA DC (per
transmitter) is required to power thecontrol loop.SeeFigure Abelow for connection of thepower supply,
transmitter and receiver.The range of appropriate receiver load resistance (RL) for the DC power supply
voltageavailableisexpressedbytheformula:
RLmax=(Vsup10V)/20mADC
Shieldedcableisrecommendedforcontrolloopwiring.
UsetheRedwire/(1)terminalasthe(+)andtheBlackwire/(2)terminalasthe().
Fig.A
Connections
CableVersion(LD30S_01Series)
 (+)= RedWire&()=BlackWire
ConduitVersion(LD30S_11Series)
(+)=Terminal#1&()=Terminal#2
WiringtoaLoopPoweredDisplay
WiringtoaTypicalPLC