User Manual
8of14 LC900008 RevA
ELECTRICAL StepFive
StrobeAlertOutput(LC30‐___2Series): Withthe
StrobeAlertwiredNC;itcanbeusedasahighorlow
level alarm, depending on the setting for the invert
switch.TheStrobeAlertcanalsobewiredNO.
Changingfrom120to240VAC:
1. Remove the two screws from the top of the
printed circuit board (PCB) and gently slide the
PCB from the housing.Use caution when
removingthePCB.
2. LocatedjumpersJWA,JWBandJWConthePCB.
3. Tochangeto240VAC,removejumpersfromJWB
and JWC and place a single jumper across JWA.
To change to 120 VAC, remove jumper JWA and
placejumpersacrossJWBandJWC.
4. Gently return PCB into housing and replace the
twoscrews.
StandardVersion(Non‐CE)
120VAC 240VAC
Configuration Configuration
CEVersion
(LC30‐10_1‐CE/LC30‐10_1‐E‐CE)
120VACConfiguration 240VACConfiguration