User Manual

RevA LC900008 7of14
ELECTRICAL StepFive
Connectingswitchestoinputterminals:PleasenoteadifferencebetweenFLOWLINEflowswitches.Allflow
switcheswillbewiredwiththeWhitewiretothe(S)terminal.ModelsFT10‐___5andGT10‐___5willbe
wiredwiththeGreenwiretothe()terminal).TheRedandBlackwirescanbewiredtoeitherthe(+)terminal
or()terminalbaseduponswitchpolarity.Seetheillustrationbelowtoindicatewiringforyourswitch.Note:
theShieldwirewillbeusedonlyforlongcablerunsorwhereexcessiveelectricalnoiseispresent.
NormallyClosed NormallyOpen
SwitchCable:Wheninstallinga Flowlineflowswitch,
adjustthecableawayfromtheprintedcircuitboards
in the controller body.Avoid breaking the seal
between the top of the level switch and the plastic
coatedcable.
VAC Power Input Wiring:Observe the labeling on
theLC30 Series.Note: Polaritydoesnot matter with
theACinputterminal.

RelayInputWiring:Therelayisasinglepole,double
throwtyperatedat250VoltsAC,16Amps.Thetwo
terminal NO and NC (normally open and normally
closed) will be used in different applications.
Remember
thatthe "normal" state is whentherelay
coilisdeenergizedandtheRedrelayLEDisOff/de
energized.
