User Manual

RevA LC900008 5of14
SAFETYPRECAUTIONS(cont.) StepThree
Make a FailSafe System: Design a failsafe system that accommodates the possibility of relay or power
failure.If power is cut off to the controller, it will deenergize the relay.Make sure that the deenergized
stateoftherelayisthesafestateinyourprocess.Forexample,ifcontrollerpowerislost,apumpfillingatank
willturnoffifitisconnectedtotheNormallyOpensideoftherelay.
While the internal relay is reliable, over the course of time relay failure is possible in two modes: under a
heavyloadthecontactsmaybe“welded”orstuckintotheenergizedposition,orcorrosionmaybuildupona
contact so that it will not complete the circuit when it should.In critical applications, redundant backup
systems and alarms must be used in addition to the primary system.Such backup systems should use
differentsensortechnologieswherepossible.
WhilethismanualofferssomeexamplesandsuggestionstohelpexplaintheoperationofFLOWLINEproducts,
such examples are for information only and are not intended as a complete guide to installing any specific
system.
Sensormount controllers:The LC30 Series is a costeffective, modular flow controller, whose body
incorporatesafemale3/4"NPT(3/4"R)fitting,allowingittobemounteddirectlyontoanyFlowlinesensoror
any3/4"connection.SimplyprovideitsrequiredACpowerandacontrolleddevicesuchasavalve,pump,or
alarmthatcanbeswitchedbythecontroller’srelayinresponsetothesensorinput.
FeaturesoftheLC30SingleInputController:TheLC30Controllerisdesignedtoreceiveasignalfromasingle
flowswitch.ItturnsitsinternalrelayOnorOff(assetbytheinvertswitch)inresponsetothepresenceofflow
ornoflow,andchangestherelaystatusbackagainwhenthesensorreverses.TheLC30maybeusedwithany
FLOWLINENchannelorrelayflowswitch.Therelayisasinglepole,doublethrowtype;thecontrolleddevice
canbeconnectedtoeitherthenormallyopenornormallyclosedsideoftherelay.Atimedelayfrom0to60
secondscanbesetbeforetherelayrespondstothesensorinput.
TypicalapplicationsfortheLC30areflowornoflowswitch/alarmoperations(activatinganalarmatnoflow).
Components:
PartNumber Thread Power CE CSA Strobe
Alert™
LC301001
¾”NPT
120
No Yes
No
LC301001CE Yes No
LC301001E
240
No Yes
LC301001ECE Yes No
LC301051
¾”Rc
120
No Yes
LC301051CE Yes No
LC301051E
240
No Yes
LC301051ECE Yes No
LC301002
¾”NPT
120
No No Yes
LC301002E 240
LC301052
¾”Rc
120
LC301052E 240
Owner’sManual
