APPLICATIONEXAMPLES StepSeven
LowFlowAlarm:Thegoalistoindicatewhentheflowratefallsbelowacertainpoint.Ifitdoes,analarmis
supposedtosound,alertingtheoperatorofalowflowcondition.
Ifpowerisaccidentallycuttothecontroller,thesensor'sabilitytonotifytheoperatorofalowflowcondition
couldbelost.Thesystemmustalerttheoperatornotonlytolowflow,buttocontrollerpowerloss.
Todothis,connectthehotleadofthealarmtotheNCsideoftherelayterminalofthecontroller.Ifpoweris
lost,therelaywillbede‐energized,andthealarmwillsound(ifthereisstillpowertothealarmcircuititself).
The alarm circuit should have a noninterruptible power supply or some other indicator or backup alarm to
warnofapowerfailureinthealarmcircuit.
In this application, the normal status is when the sensor is in the flow condition, and the relay will be
energizedholdingthealarmcircuitopen.Pleasenotethattheflowswitchcanbewiredeithernormallyclosed
ornormallyopen(Step5).WhentheswitchiswiredNC,theinputLEDwillbeoffandtherelayLEDwillbeon.
Sofor this application,Invertshouldbe settotheOn position.Whentheswitch iswiredNO, the inputLED
andtherelayLEDwillbeonsimultaneously.Soforthisapplication,InvertshouldbesettotheOffposition.
LEDIndication:UseLED'slocatedabovetheinputterminalstoindicatewhethertheswitchisinafloworno‐
flow state. When the switch is wired NC, Amber indicates no‐flow and Off indicates flow. Reversing the
polarity(NormallyOpen),AmberindicatesflowandOffindicatesno‐flow.
NormallyClosed(NC)
AmberLEDONforNo‐Flow
NormallyClosed(NC)
LEDOFFforFlow
NormallyOpen(NO)
AmberLEDONforFlow
NormallyOpen(NO)
LEDOFFforNo‐Flow
FlowSwitchLEDON
forNo‐Flow
FlowSwitchLEDOFF
forFlow
FlowSwitchLEDOFF
forFlow
FlowSwitchLEDON
forNo‐Flow
Note:TheLEDinsidetheflowswitchwillalways
beONforNo‐FlowandOFFfor Flow,regardlessofthepolarity
ofthe flow switch.In NCwiring,the switch’sLED will match the controller’sLED.InNO wiring, theswitch’s
LEDwillbeoppositeofthecontroller’sLED.