INSTALLATION(continued) StepSix
4. Mechanicalconnectiontoconduit:Allwiringbetweenacontrollerandsensorsshouldbeinconduit.
The power entrance of the controller is a standard ½” NPT female fitting that will attach to standard
electrical conduit, either plastic or metal, as specified by local codes.Keep in mind that the housing
mayhavetobeunscrewedfromthesensorforperiodiccleaningofthesensor.Forthisreasontheuse
offlexibleconduit,providingenoughslackforeasyaccessisrecommended.
5. Connecttheextensionwiring:
Beforemakingconnections,makesureallpowertothesystem(controller,motor,valve,alarm,etc.)
isOFFwithasafetylockoutonthecircuitbreaker.
a. Theextensionwiringtocontrollershouldtakeintoaccountlongcableruns.Iftherunislong, it
mayneedtobeaslightlythickergaugesotheseriesresistanceiskelpwithinallowablelimits.
b. Threadtheextensionwiringthroughthepowerconduitentranceofthehousing.
c. Strip¼”oftheinsulationfromtheendsofthewires.
d. Loosen the appropriate terminal screws.Insert the extension wires into the corresponding
terminals,matchingthesensorwires.
e. Tightentheterminalscrews.
f. Return the wire protector to its location and restore the final screw which holds the wire
protectedandPCBinitsplace.
g. Replacethecap.
Note:Insome cases,additional user‐providedcomponents mayneedto beattachedtothe terminals.If
so, make sure that both wires and/or components entering the terminal are secure after the screws are
tightened.
Note:Alwaystightenthecontrollerfromthewrenchflatlocatedonthe
swivelbase.Nevertightenfromthebodyofthecontroller.