Product Brochure

5
Reliance Detection Technologies, LLC
27 Business Park Drive
Branford, CT 06405
203-488-2684 or 888-771-4929
info@RelianceDetection.com
www.RelianceDetection.com
© 2019 Reliance Detection Technologies, LLC – A Madison Company – All specications are subject to change without notice. RDT_SubmittalSheet_RSC-900_012019_RevB
RSC-900 TECHNICAL SUBMITTAL DATA SHEET
DIMENSIONS & WEIGHTS:
AVAILABLE ACCESSORIES (see pg. 6):
Extra Wireless Water Flood Sensors (RSC-900-W-001)
Wireless Rope-Style Water Sensor Kit (RSC-900-W-175)
Wireless Signal Repeater (RSC-900-X-200) – Max. 2 per system
Extra Wireless Actuator & Valve (RSC-900-W-310-X)
RDT recommends that RSC-900-AW installations be completed by a licensed plumber to ensure that all local code requirements are followed.
RSC-900 Shut-Off Valve Specications
Size
Square
A B C D E F G H I L CH M P CV PSI LBS
IN-LBS
1/2” 1.50 1.28 0.35 1.42
(ISO F03)
0.24 0.35 0.08 0.98 1.32 0.59 2.64 1.06 0.22 0.56 18.84 580 0.21 53.10
3/4” 1.50 1.36 0.35 1.42
(ISO F03)
0.24 0.35 0.08 0.98 1.57 0.64 2.99 1.26 0.22 0.75 34.10 580 0.40 53.10
1” 1.50 1.79 0.35 1.42
(ISO F03)
0.24 0.35 0.12 0.98 1.93 0.75 3.54 1.61 0.24 0.95 49.71 580 0.75 53.10
1-1/4” 1.50 1.93 0.35 1.42
(ISO F03)
0.24 0.35 0.12 0.98 2.30 0.84 4.02 1.97 0.24 1.18 102.88 580 1.05 53.10
ORDERING INFORMATION:
Valve Size
P/N UPC
1/2”
RSC-900-AW-1/2 811475030078
3/4”
RSC-900-AW-3/4 811475030085
1”
RSC-900-AW-1 811475030092
1-1/4”
RSC-900-AW-1-1/4
811475030108
None RSC-900-W
811475030177
OPERATING SPECIFICATIONS:
See charts at right for further detail.
Valve
Pressure Rating ..........
600 WOG - 150 WSP
Max. Temperature.......366°F
Actuator
Max. Pressure ............80 PSI
Sensor
Audible Alarm ............83 dB
MATERIALS:
Valve
Body ...................Low-lead brass
End Connection ...Low-lead brass
Stem ...................Low-lead brass
Ball .................... Low-lead brass
(tea coated)
Ball Seats ............PTFE
O-Rings ............... FKM (Viton
®
)
CABLE LENGTHS:
Hub Power Cord ..5’
Ethernet Cable .....4’
APPROVALS:
(IN-LBS) TORQUE VALVES ARE MEASURED IN LABORATORY TESTS UNDER THE FOLLOWING CONDITIONS: TEMPERATURE: 68°F;
PRESSURE: 0 PSI; FLUID: PURIFIED WATER.
Shut-Off Valve
Communications Hub
Wireless Sensor
7.75
6.73
2.16
5.25
7.75
6.73
2.16
5.25
R.61
1.25
4.00
12.00
LEAD
LENGTH
1.40
1.00
1.08
.47
.70
Wireless Actuator
5.60
1.96
1.80
2.90
1.75
3.50
SECTION A-A
A
A
SQUARE
L
E
A
M
CH
Ø H
90°
B
NPT
F
I
Ø P
Ø C
Ø G
SQUARE
4X Ø D
THRU
RSC-900 Wireless Component Specications
Component Weight* Power Supply
Backup
Battery
Primary Radio
Frequency
Operating
Temperature
Communication
Signal
Range
Addressable?
Communication
Hub
6 oz
(170 gm)
External Adapter
Input 110-240V AC
(2) AA
batteries
915 MHz
-4°F to 122°F
(-20°C to 50°C)
Wi-Fi, Ethernet 200’ Yes
Wireless
Actuator (IP68)
13 oz
(369 gm)
(4) CR123A batteries
2-year life
N/A 915 MHz
-4°F to 122°F
(-20°C to 50°C)
Wireless RF 200’ Yes
Wireless
Sensor
2 oz
(57 gm)
(2) AAA batteries
2-year life
N/A 915 MHz
-4°F to 122°F
(-20°C to 50°C)
Wireless RF 200’ Yes
* Weight without accessories attached.
RSC-900 Wireless System FCC & Industry Canada Info
This device complies with Part 15 of the FCC Rules. Operation
is subject to the following two conditions: (1) this device may
not cause harmful interference, and (2) this device must accept
any interference received, including interference that may
cause undesired operation.
Communication Hub: IP Rating IEC60529
Valve/Actuator:
IP Rating IEC60529; IP68; ANSI
61/372 (Valve)
MA Board of Registration of Plumbers Approval –
Code # P1-1018-40 (System)
Certications: FCC IC
Flood Sensor 2AFOICLMFLD10 20798-CLMFLD10
Hub 2AFOICLMCTRL10 20798-CLMCTRL10
Actuator 2AFOICLMASOU20 20798-CLMASOU20
TECHNICAL SUBMITTAL DATA SHEET
Wireless, App-Based Plumbing Leak Detection &
Optional Automatic Water Main Shut-Off System