© 2018 Reliance Detection Technologies, LLC – A Madison Company – All specications are subject to change without notice. RDT_SubmittalSheet_RS-080_Buttery_102018_RevA
RS-080 with 2-1/2” to 4” Buttery Valve TECHNICAL SUBMITTAL DATA SHEET
DIMENSIONS & WEIGHTS:
RDT recommends that installations be completed by a licensed plumber to ensure that all local code requirements are followed.
ORDERING INFORMATION:
OPERATING SPECIFICATIONS:
Buttery Valve
Pressure Rating ..........
250 PSI
Max. Temperature.......250°F
Electric Actuator
Voltage ......................24V AC
Absorbed Current .......1.0 A
Absorbed Power .........24V A
Frequency ..................50/60 Hz
Working Temp. ...........-4° to 131°F
Receiver Box
Audible Alarm ............83 dB
MATERIALS:
Buttery Valve
Body ...................Ductile Iron
Seat .................... EPDM (-30° to 250°F)
Lug Style
Disc .................... Nylon-Coated
Ductile Iron
Shafts ................. 416 Stainless Steel
Locating Pin ........ Carbon Steel
Bushing ..............PTFE
O-Ring .................EPDM
Mounting ............ Direct Mount* (see note
under Dimensions)
CABLE LENGTHS:
Power Cord .........12’
Sensor Cable ....... 8’
(custom lengths avail.)
Valve Cable ......... 8’ (adder lengths avail.)
APPROVALS:
NSF/ANSI 61 and 372 approved valve.
MA Board of Registration of Plumbers
Approval – Code # P3-0818-66.
UL classied actuator.
RS-080 Shut-Off Buttery Valve Specications: 2-1/2” through 4”
Size
C
ISO
B1 A B2 L D E H R DO K Z-d g F D1 N-TH LBS
Seat Torque CV
(GPM @ 1 PSI)
100 PSI 200 PSI 50% OP
100% OP
2-1/2” F05 9mm 6.89 3.50 1.76 2.54 0.47 15.04 10.63 0.50 3.03
4-0.28
1.38 0.12 5.49
4-5/8”-11
9.3 134 167 65 220
3” F05 9mm 7.13 3.74 1.78 3.10 0.47 15.51 10.63 0.50 3.03
4-0.28
1.38 0.12 6.00
4-5/8”-11
10.4 205 223 70 300
4” F07
11mm
7.87 4.49 2.05 4.09 0.63 17.00 10.63 0.62 3.54
4-0.35
2.17 0.12 7.50
8-5/8”-11
19.8 339 386 140 605
Valve Size P/N UPC
2-1/2” RS-080-2-1/2 857640005786
3” RS-080-3 857640005793
4” RS-080-4 857640005809
SECTION A-A
A
A
Ø3.10
F
Øg
B
ØC
Z-d
ØK
L
D1
Ødo
ØD
H
N°TH
E
A
B
SECTION A-A
A
A
Ø3.10
F
Øg
B
ØC
Z-d
ØK
L
D1
Ødo
ØD
H
N°TH
E
A
B
Shut-Off
Buttery Valve
(2-1/2” to 4”)
1234
A
B
SIZE
DWG NO
REV
SCALE
SHEET
OF
DRAWN
TITLE
PROPRIETARY INFORMATION
THE INFORMATION
CONTAINED IN THIS
DOCUMENT IS THE PROPERTY
OF MADISON COMPANY. IT IS
SUBJECT TO RETURN UPON
DEMAND AND MAY NOT BE
REPRODUCED OR
OTHERWISE DISCLOSED
WITHOUT WRITTEN
PERMISSION FROM MADISON
COMPANY.
UNLESS OTHERWISE
SPECIFIED DIMENSIONS ARE
IN INCHES
TOLERANCES
FRACTIONS: ±1/64
ANGLES: 1°
DRAFT ANGLE: 1/2°
XXX: ±.005 XX: ±.01
X: ±.
1
DRAWING INTERPRETED
PER ANSI Y 14.5
CODE IDENT NO.
21603
NONE
RS- 094 LEAK DETECTION SYSTEM
RS-094 Assmebly
3
4
A
B
MADISON COMPANY
27 Business Park Drive, Branford, CT 06405
SFM 6/25/2018
3.0
"UNIVERSAL SENSOR PUCK"
8 FT LEAD
Ø 3.0
Water Sensor
1.08
2.61
2.65
.3
3
2.
06
1.17
2.66
AH
P
G
C D
E
B
F
RS-080 Electric Actuator Specications
Size
Drilling
ISO 5211
A B C D E F G H I P
2-1/2”, 3”, 4” F03-F05 6.18 7.40 2.38 5.12 5.75 1.65 1.30 1.42 0.47 2.68
Receiver Box
Actuator
AVAILABLE ACCESSORIES (see pg. 26):
• Wired Sensor Pucks – Up to 5 additional sensors can be wired to a single RS-080 receiver
box for a wider area of leak detection.
• Sensing Rope Kit – Ideal for use with low tanks, or for room perimeter and sub-oor leak
detection applications.
• Auto Dialer – Receive automatic alerts whenever the RS-080 identies a fault condition.
• Cable Adder – Allows for positioning of the RS-080 receiver up to 100’ further away
from the valve.
Note: Buttery valves
require appropriate
mounting ange
and hardware (not
included). Please
see install manual
for details.
Recommended ange:
316/316L SS forged,
threaded NPT-F,
150 lb. ANSI raised-
face ange (raised