Demand Control Ventilation System Installation, Operation, and Maintenance Manual RECEIVING AND INSPECTION Upon receiving unit, check for any interior and exterior damage, and if found, report it immediately to the carrier. Also check that all accessory items are accounted for and are damage free. WARNING!! Installation of this control panel should only be performed by a qualified professional who has read and understands these instructions and is familiar with proper safety precautions.
TABLE OF CONTENTS Demand Control Ventilation System ............................................................................................................. 1 Installation, Operation, and Maintenance Manual ........................................................................................ 1 WARRANTY .................................................................................................................................................. 3 SAFETY INFORMATION ................................
WARRANTY This equipment is warranted to be free from defects in materials and workmanship, under normal use and service, for a period of 12 months from date of shipment. This warranty shall not apply if: 1. The equipment is not installed by a qualified installer per the MANUFACTURER’S installation instructions shipped with the product, 2. The equipment is not installed in accordance with federal, state and local codes and regulations, 3. The equipment is misused or neglected, 4.
SAFETY INFORMATION General This control panel utilizes a mixture of traditional controls along with a “smart” digital circuit board controller, referred to as the ECPM03 control board. It is intended to be installed within a UL508A electrical control package. The board is powered by 24 Volts DC, which is provided by an approved 10-20 Watt class 2 power supply included inside the panel. Some parts of the ECPM03 circuit board can be electrically live and some surfaces can be hot.
FIELD WIRING: The following is for reference only. All 120 Volt AC field wiring is landed on terminal blocks, not on the board itself. See Installation section for details. Low voltage class 2 field wiring may be landed at J3, J4, J5, or J10 connectors only, as indicated by the panel labeling and installation schematic. Provision for spacing and routing of the field wiring is provided in the panel.
INSTALLATION It is imperative that this unit is installed and operated with the designed airflow and electrical supply in accordance with these manual and applicable codes. If there are any questions about any items, please call the service department at 1-866-784-6900 for warranty and technical support issues. Mechanical WARNING: DO NOT LIFT CONTROL BY WIRING COMPONENTS Site Preparation 1. Provide clearance around installation site to safely install equipment into its final position.
Wall Mount Installation (Optional) Mount control panel with adequate clearance from excessive heat sources such as appliances to prevent damage of the components. Duct Sensor Installation When the control panel is ordered, the system typically consists of one duct sensor per hood exhaust riser. These sensors are typically shipped factory installed in factory assembled hood risers. If the risers are field cut, the sensor and other components are shipped loose for field installation as shown below.
Electrical Before connecting power to the control, read and understand this entire document. As-built wiring diagrams are furnished with each control by the factory and are attached either to the door of the unit or provided within a paperwork pouch internal to the panel. Electrical wiring and connections should be done in accordance with local ordinances and the National Electric Code, ANSI/NFPA70.
Low Voltage Wiring Low voltage field wiring consists of Duct and Room Temperature sensors, ECM motors, 0-10VDC output, 24VDC input, or Modbus communication over CAT-5 cables for HMI(s) and remote equipment. Additionally, panels can be ordered with Building Management Options. Refer to the Building Management Owner’s Manual, if equipped, for low voltage building management wiring requirements.
Variable Frequency Drive (VFD) Installation Instructions Input AC Power 1. Circuit breakers feeding the VFDs are recommended to be thermal-magnetic and fast acting. They should be sized 1.25 to 1.5 times the input amperage of the drive. Refer to the installation schematic for breaker sizing. 2. Each VFD should be fed by its own breaker. If multiple VFDs are to be combined on the same breaker, each drive should have its own protection measure (fuses or miniature circuit breaker) downstream from the breaker.
ACTECH SMV VFD CROSS-REFERENCE TABLE Model Number ESV751N01SXB571 ESV112N01SXB571 Volts 120/ 240V 120/ 240V ESV371N02YXB571 ESV751N02YXB571 ESV112N02YXB571 ESV152N02YXB571 ESV222N02YXB571 ESV402N02TXB571 ESV552N02TXB571 ESV752N02TXB571 ESV113N02TXB531 ESV153N02TXB531 240V 240V 240V 240V 240V 240V 240V 240V 240V 240V ESV751N04TXB571 ESV112N04TXB571 ESV152N04TXB571 ESV222N04TXB571 ESV402N04TXB571 ESV552N04TXB571 ESV752N04TXB571 ESV113N04TXB531 ESV153N04TXB531 ESV183N04TXB531 ESV223N04TXB531 ESV751N06TXB5
OPERATION Start-Up Procedure NOTE: FIRE system must be in ARMED state before proceeding. 1. Once all required connections have been completed as indicated on the installation schematic, startup can begin. Apply power to the panel. The ECPM03 board and the HMI(s) will power up and beep. If that is not the case, check all power connections. Verify that there is no alarm message displayed on any HMI. If there are alarms present, you can press the MUTE button to silence the alarm and then work to resolve them.
6. If the controls include the Self Cleaning or CORE Protection Fire System option, a WASH button will be displayed on the HMI. Push the button to start the wash cycle. Water will be sprayed in the plenum and duct of the hood and surfactant will be injected at a predetermined frequency. The wash cycle will stop when the wash timer expires or when the Stop Wash button is pressed. Make sure Hood filters remain in place during the wash cycle.
Max Air Flow: By manually pressing the MAX AIR button, the fans will run at High Frequency, typically 60 Hz for a factory set time of 30 minutes. This time is adjustable under the Misc Options section of the configuration menu. Once the time period has expired or if the MAX AIR button is pressed again, the VFDs will go back to operating based on the duct temperature.
Functionality Fan Control The control panel controls fans through VFDs. They are used to adjust the speed of 3 phase motors and frequency is proportional to airflow. There is one VFD for each fan in the system. Preparation Time Mode 1. This option is enabled by default from the factory. It can be disabled under Configuration → Factory options. 2. Preparation Time Mode is available for morning operation when appliances are off or when very light food preparation is performed.
If the signal from the make-up air is not received by the DCV 90 Sec (factory default) after the start signal is sent to the supply fan, an alarm will appear on the HMI. The DCV panel ships with a jumper between terminals IL1A and IL1B for supply #1 and IL2A and IL2B for supply #2 if present. The jumper has to be removed first before wiring the interlock from a make-up air unit.
The amount of time elapsed since the previous wash cycle is greater than the “Wash Min Interval time” value configured under “Misc Options”. That elapsed time is reset to zero when the wash cycle is run. c. If a Building Management System (BMS) is remotely controlling the fans through the external input terminal IO1, when the Fans are turned ON and then OFF through the IO1 terminal, granted that the fans are not maintained on by the duct temperature sensors or the fan button. d.
Shunt Trip Follow Fans (Optional) If this option is ON, the shunt trip will be energized whenever the fans are off. This is meant to prevent electric cooking appliances from running when the fans are off and is only required in some jurisdictions. This option can be enabled under Configuration/Misc Options/Shunt trip Follow Fans. Factory Default Setting is OFF. Dimmable HMI (Optional) This option allows the backlight on all HMIs to turn off whenever a timer is satisfied.
Configuration and Diagnostics Security 1. To access the Configuration / Factory, the password 1111 must be used. 2. To access the Configuration / Fire Options, the password 1234 must be used. Setup Options The ECPM03 board allows the user to monitor the system and configure a broad range of options associated with the functionality of the system. Monitoring is done through the setup menus on the ECPM03 LCD as shown above.
c. Display temperature readings Starting from the Main menu, press the DOWN button. Screen displays “Temperatures”. Press the ENTER button. Press the UP and DOWN buttons to view all temperatures measured by the room and duct temperature sensors. d. Display Fan Monitoring data: Fan Frequencies and Motor Amps Starting from the Main menu, press the DOWN button until the screen displays “Monitoring”. Press the ENTER button. Press the UP and DOWN buttons to alternate between “Fan Frequencies” and “Motor Amps”.
h. Configure Misc. Options: 1. Enable Electric Gas Valve control This option will be enabled by default if the system is equipped with CORE Protection Fire system. Starting from the Main menu of HMI, press DOWN or UP until the screen displays “Misc Options”. Press ENTER. Press UP or DOWN until the screen displays “Set Gas Valve”. Press ENTER. Press UP or DOWN to turn this option ON or OFF. Press ENTER. Press MENU multiple times to get back to the main menu or one more time to reboot the processor. 2.
7. Set 0-10VDC output (Factory Default: Exhaust CFM Ratio): In addition to each variable frequency drive (VFD) in the DCV system providing a 0-10 VDC analog output from its terminals 30 and 2 directly proportional to its Fan Speed Ratio (Fan Frequency / Fan High Frequency), the ECPM03 also offers a 0-10VDC output from terminals VOand VO+. This output can be configured depending on the type of signal needed by the building management system or the equipment receiving it.
11. Set Wash Min Fan Runtime (Factory Default: 480 min): This option is available if the control system includes self-cleaning option from the factory. Its maximum value is 1440 minutes or 24 hours. Refer to the Self-Cleaning Section under Functionality for more details about this option. Starting from the Main menu of HMI, press DOWN or UP until the screen displays “Misc Options”. Press ENTER. Press UP or DOWN until the screen displays “Set Wash Min Fan Runtime”. Press ENTER.
Press MENU multiple times to get back to the main menu or one more time to reboot the processor. 17. Set Min Prep Frequency(Factory Default: 10Hz) This option is only displayed when Prep Time Mode is enabled. Its maximum value is the minimum of the low frequencies of all the fans controlled by the package and minimum value is 5Hz. Starting from the Main menu of HMI, press DOWN or UP until the screen displays “Misc Options”. Press ENTER. Press UP or DOWN until the screen displays “Set Min Prep Frequency”.
j. Configure Fan Options This sub-menu contains all options related to Fan configuration. Starting from the Main menu of HMI, press DOWN or UP until the screen displays “Fan Options”. Press ENTER. Press UP or DOWN until one of the options below is displayed. Press ENTER to access that option. Press UP or DOWN to select the fan (EXH1, EXH2, SUP1 etc.). Press ENTER. Press UP or DOWN to change the value of that option for that fan.
k. Configure the Fire Options This sub-menu is Password protected and changes should not be made after passing an inspection. Starting from the Main menu of HMI, press DOWN or UP until the screen displays “Fire Options”. Press ENTER. When prompted, enter the password specified under the security section of this manual above. Press UP or DOWN until one of the options below is displayed. Press ENTER to access that option. Press UP or DOWN to change the value of that option.
4. Set Number of Fan Switches This defines the number of fan switches controlled by the system. There can be 0 or 1 fan switch. A fan switch will be displayed on the HMI accordingly. If 0 is selected, the fans will be only controlled by the temperature sensors. 5. Set Number of Light switches This defines the number of hood light switches controlled by the system. There can be 0, or 1 light switch. A light switch will be displayed on the HMI accordingly. 6.
Component Description Variable Frequency Drive Variable frequency drives change the speed of 3 phase motors by changing the frequency signal sent to the motor. There is one variable frequency drive for each fan in this system. 2 RJ-45 plugs are used to connect the drives to each other and to the ECPM03 controller through CAT-5 cables. Variable Frequency Drive Parameters Variable frequency drive parameters can be changed with the buttons on the face of the drive.
o o Pin 1 positive side of the 24 Volt DC input to the board Pin 2 – 7 Open collector outputs, 100ma max each, suitable for driving 24VDC relays or indicator lamps. o Pin 8 – 12 4-20ma current inputs. 150 Ohm impedance to 24 VDC ground pin 14. o Pin 13 Chassis ground connection, this pin connects to the 24VDC ground through a paralleled 1000pf 2000V cap and a 100k Ohm 1/4W resistor.
Temperature Sensor The temperature sensor is a 10K Ohm Thermistor. The sensor gives constant feedback to the controller. One sensor is installed in every riser. Room Temperature Sensor The Room temperature sensor is a 10K Ohm Thermistor. The sensor provides constant room temperature to the controller. It should be installed on a wall somewhere in the space but not directly under the hood or close to an appliance so that the reading is not affected by heat.
Troubleshooting The following table lists causes and corrective actions for possible problems with this control. Review this list prior to consulting manufacturer.
The following table lists Fault messages displayed on the HMI and corrective actions. Review this list prior to consulting manufacturer. Fault Message on HMI “Fire” “Equipment Disable High Temp” Potential Cause FIRE or fire circuit not wired properly. Duct temperature exceeded the High Temp Equipment shutdown Threshold and shut down the gas valve and energizes the shunt trip. “Light Fault Zone 1 Bx De-energized” Light output is energized but no power is detected on terminal B1.
MAINTENANCE To guarantee trouble free operation of this control, the manufacturer suggests following these guidelines. Most problems associated with unit failures are directly related to poor service and maintenance. Please record any maintenance or service performed on this equipment in the documentation section located at the end of this manual. WARNING: DO NOT ATTEMPT MAINTENANCE ON THIS CONTROL UNTIL THE ELECTRICAL SUPPLY HAS BEEN COMPLETELY DISCONNECTED General Maintenance 1.
Start-Up and Maintenance Documentation START-UP AND MEASUREMENTS SHOULD BE PERFORMED AFTER THE SYSTEM HAS BEEN AIR BALANCED (Warranty will be void without completion of this form) Job Information Job Name Address City State Zip Phone Number Fax Number Contact Purchase Date Service Company Address City State Zip Phone Number Fax Number Contact Start-Up Date Maintenance Record Date Service Performed Factory Service Department Phone: 1-866-784-6900 Fax: 1-919-554-9374 34 A0023662 May 2014 Rev.
A0023662 May 2014 Rev.
A0023662 May 2014 Rev.