95 North Oak Street • Kendallville, IN 46755
MAGNETIC STARTERS FOR 3 WIRE FRANKLIN MOTORS
Overload Protection • 4”, 6” & 8” Submersible Motors – 60 Cycle – 3 Phase
MOTOR
SIEMENS/FURNAS CLASS 16
STARTER HEATER
HP VOLTS F&W PART NO. Size Full Load AMPS F&W PART NO. SIZE F&W PART NO.
4” FRANKLIN SUBMERSIBLE MOTORS – 60 HZ – 3 PHASE
1 1/2
200 137457
25
139324
K43 130274
230 137458 K41 130272
460 137460 139325 K29 134872
2
200 137461
25
139324
K50 133010
230 137462 K43 130274
460 137464 139325 K33 130275
3
200 137465
25
139324
K54 130282
230 137466 K52 130276
460 137468 139325 K37 130277
5
200 137469
25
139324
K61 133016
230 137470 K61 133016
460 137472 139325 K49 130280
7 1/2
200 137473
25
139324
K68 130288
230 137474 K67 133020
460 137476 139325 K55 133013
6” & 8” FRANKLIN SUBMERSIBLE MOTORS – 60 HZ – 3 PHASE
5
200 133492
25 139324
K61
133016
230 133493 K61
460 133494 25 139325 K49 130280
7 1/2
200 130646 30 139326 K68 130288
230 126552 25 139324 K67 133020
460 128876 25 139325 K55 133013
10
200 130647
40 139327
K72 131724
230 126554 K70 133018
460 128875 25 139325 K58 130279
15
200 130648 60 139328 K76 130691
230 126555 50 139329 K75 130293
460 128884 25 139325 K64 130281
20
200 130649
75 139330
K78 130289
230 128754 K77 130287
460 128888 40 139331 K69 135548
25
200 130650 120 139332 K86 131725
230 128755 90 139333 K83 133021
460 128890 40 139331 K72 131724
30
230 128964 120 139332 K87 135549
460 128965 50 139334 K74 130285
40 460 021003 75 139335 K77 130287
50 460 021004 90 139336 K83 133021
60 460 023029 91 023032 K87 135549
75* 460 023030 107 023032 K89 023034
100* 460 023031 142 023033 K94 023035
*Denotes 8” motor
CAUTION: WARRANTY ON THREE PHASE SUBMERSIBLE MOTORS IS VOID UNLESS PROPER
QUICK TRIP PROTECTORS ARE USED ON ALL 3 LEAD WIRES.
The characteristics of submersible motors are different from standard motors and special overload protection is required. If the motor is
stalled, the overload protector must trip within approximately 10 seconds to protect the motor windings. In the three phase submersible
motors, the installer must provide the SPECIAL EXTRA QUICK TRIP PORTECTORS AS TABULATED. The heaters given are for ambient
compensated starter boxes; if they are not used, nuisance tripping (over protection) may be experienced at high temperatures and no
protection will exist at low temperatures.
Overload protectors (heaters) for motors of “200-230 volt” ratings should be selected for each installation based on the line voltage
measured at the control panel.