8. Fault handling
No. Error description Check Possible reasons Action
1 Guide unit not moving a. Check automatic fuses
b. Check relay One relay should pull when running.
c. Total cable length Cable length too long. The total cable length from box through Guide units is not allowed to
exceed 20 meters.
d. Number of Guide units connected The total number of Guide units should not exceed 10 in each
direction.
e. Are the guide rails attached to the
Guide units without any stress?
Conveyor not horizontal.
Guide units not parallell to each
other.
Check conveyor with water level.
Check Guide units with scale and composing stick.
2 Guide unit moving the wrong direction a. Connectors Loose Guide unit connector Secure that connectors are connected correctly.