User's Manual
Chapter 4: Connecting the Power System
2.
Connect the ground cable to the connectors with 2 AWG wire with a 2–hole lug for a 1/4”
diameter stud. See Figure 4-14: Ground Bus Bar.
Figure 4-14: Ground Bus B ar
3.
Fasten the lug onto the stud with the nuts provided. Tighten the nuts to 40–50 in-lb torque.
4.
Connect the other end of the cable to the master ground bar or other suitable ground source
available at the installation site.
RadioRouter Base Station Indoor Installation Guide © 2005 Flarion
Flarion Proprietary and Confidential
Page 4-14