Installation Guide

CLEARANCES — CGI603D MODELS
CLEARANCE DIMENSIONS
CGI603D
MM
A Minimum clearance from top of trivets to:
z
Rangehood 650
z
Overhead exhaust fan 800
z
Downward facing combustible surface* 650
z
Downwards-facing tiled or fire resistant surface 500
B Minimum clearance below bench top to:
z
Combustible surface 70
z
Fisher & Paykel oven or nearest non-combustible surface 65
C Minimum clearance from side of cutout to nearest adjacent combustible surface 115
D Minimum distance from right edge of cooktop to gas connection point on wall
(if using a flexible hose)
250
E Distance from floor to gas connection point on wall
(if using a flexible hose)
800-850
F Minimum clearance from countertop to overhead cabinet
(not directly above the cooktop)
450
G Maximum depth of overhead cabinetry 600
H Minimum distance between overhead cabinets
(centered above cooktop)
600
I Minimum clearance from rear edge of cutout to nearest:
z
Combustible surface 85
z
Non-combustible surface 45
A
H
f f
b
C
C
D
E
g
i
*Combustible surface definition
Any materials of a building structure or decorative structure made of wood, compressed paper,
plant fibres, vinyl/plastic or other materials that are capable of transferring heat or being
ignited and burned. Such material shall be considered combustible even though flame-proofed,
fire-retardant treated or surface-painted, or plastered.
Ensure there is an earthed power outlet within 900mm of the centre rear of the product. The gas
connector on the wall should be accessible with the product installed.
10