Overview of Primary Product

22
£
TEST PROCEDURES
INTRODUCTION
This section describes the test procedures that must be performed after installation to insure that the
Multi-Burner Control is operating properly; these procedures are mandatory.
LIMITS AND INTERLOCK TESTS
Periodically check all interlock and limit switches by manually tripping them during burner opera-
tion to make sure they cause the system to shut down.
The burner at which a flame fails will be identified by a red “Flame Failure” LED on the corre-
sponding MB-600PF flame sensing module.
FLAME SIGNAL STRENGTH
Insert the positive probe of a 0-15 VDC, one megohm/volt
(minimum) meter into the test point on the MB-600PF as
applicable, shown in the photo at left. Connect the negative
probe to ground. A good flame signal strength will read
between 6 and 11 VDC; anything below 4 VDC is inadequate.
MINIMUM PILOT TEST
Run the following test procedures to ensure that the sensor
will not detect a pilot flame too small to reliably light the main
flame:
1.Manually shut off the fuel supply to the burner, but not to the
pilot.
2.Start the system normally.
3.To enter the pilot test mode, press the RESET and ENTER
buttons simultaneously. Then release the RESET button but
keep the ENTER button depressed for another 10 seconds. The
Limits LED will blink, signaling that the system is in the pilot
test mode.
4. The control will hold the operating sequence at the pilot flame step. Measure signal strength as
described above.
5. Reduce pilot fuel until the flame relay drops out. Increase pilot fuel until the flame signal is
greater than 4 VDC, and flame relay just manages to pull in. This is the minimum pilot. If you
don’t think this flame will be able to safely light the main burner, realign the sensor so that it
requires a larger pilot flame and repeat steps 2 through 5.
6. Push the RESET button to exit the test mode and begin the normal start-up sequence again.
7. When the sequence reaches the main flame trial for ignition, smoothly restore the fuel supply to
the burner. If the main burner does not light within five seconds, immediately shut off the burner
supply to shut down the system. Realign the sensor so that it requires a larger pilot flame. Repeat
steps 1 through 6 until the main burner lights off smoothly and reliably.
WARNING: Never operate a system that is improperly adjusted or has faulty interlocks or
limit switches. Always replace faulty equipment with new equipment before resuming oper-
ation. Operating a system with defective safety equipment can cause explosions, injuries,
and property damage.
FIGURE 7.
Voltmeter Hookup to Measure