Overview of Primary Product

2
£
MBSERIES SPECIFICATIONS
ELECTRICAL RATINGS
VA ratings (not specified as pilot duty) permit the connection of transformers and similar devices
whose inrush current is approximately the same as their running current.
VA Pilot Duty ratings permit the connection of relays, solenoid valves, lamps, etc. whose total oper-
ating load does not exceed the published rating and whose total inrush current does not exceed 10
times the rating.
Running and locked rotor ratings are intended for motors. VA and VA Pilot Duty loads may be
added to a motor load provided the total load does not exceed the published rating.
PARAMETER DESCRIPTION
SUPPLY VOLTAGE 120 VAC (+10%, -15%), 50/60 Hz
POWER COMSUMPTION 25 VA
TEMPERATURE RANGE
UNIT MODEL NO TEMPERATURE RANGE
MULTI-BURNER MB-600S -40° TO +60°C (-40° TO +140°F)
FLAME SENSOR MB-600PF -40° TO +60°C (-40° TO +140°F)
REMOTE DISPLAY MB510 0° TO +50°C (-32° TO +122°F)
UV SCANNER UV7A4 -40° TO +125°C (-40° TO +257°F)
90° UV SCANNER UV7R4 -40° TO +60°C (-40° TO +140°F)
SELF-CHECK UV UV7SC -40° TO +60°C (-40° TO +140°F)
FLAME FAILURE RESPONSE 3 SECONDS (+/-) 0.5 SECONDS)
PILOT TRIAL FOR IGNITION 5, 10 OR 15 SECOND SELECTABLE
PILOT PROVING TIME 5 SECONDS
MAIN TRIAL FOR IGNITION FOLLOWS PILOT TRIAL FOR IGNITION SELECTION
PURGE TIME PURGE: SELECTABLE 0-225 SEC., 15 SEC. INCREMENTS
WITH X4 0-15 MIN., 1 MIN. INCREMENTS
EXTENDED: SELECTABLE 0-15 MIN., 1 MIN. INCREMENTS
WITH X4 0-60 MIN., 4 MIN. INCREMENTS
CONTACT RATINGS
AT 120VAC
(MAXIMUM TOTAL CON-
NECTED LOAD NOT TO
EXCEED 15 AMPS
FUNCTION AFFECTED TERMINALS INDUCTION LOAD RESISTIVE LOAD
FAN MOTOR J2-3 1/2 HP 15 AMPS
VALVE RELAYS J2-4 THROUGH J2-6 1/3 HP 10 AMPS
LEAK DETECT J2-7 1/3 HP 10 AMPS
ALARM RELAY J2-8 1/3 HP 10 AMPS
MODULATION J3-1 THROUGH J3-4 1/3 HP 10 AMPS
APPROVALS UL RECOGNIZED, US and CANADA (FILE MP1537)
FM APPROVED (FILE 3013812)
SHIPPING WEIGHT 7 KILOGRAMS (15 IBS.)
CAUTION: Published load ratings assume that no contact be required to handle inrush cur-
rent more often than once in 15 seconds. The use of control switches, solenoid, relays, etc.
which chatter will lead to premature failure. It is important to run through a test operation
(with fuel shut off) following the tripping of a circuit breaker, a blown fuse, or any known
instance of chattering of any external current consuming devices.