Product Overview

2
REMOTE DISPLAY
The MicroM provides an interface to the optional ED510 display module. The ED510 connects to
the MicroM through the plug-in board using a ED580 cable. The ED580 cable is available in 2, 4, or
8 foot lengths. Part number 129-145 -1 (4 ft.), -2 (8 ft.), -4 (2 ft.) is available for remote mounting the
ED510 Display Module.
The ED510 Display Module is a backlit, 2 line by 16 character LCD display with keypad to provide
both current operation and historical information of the MicroM. The ED510 contains a keypad con-
sisting of three push keys, SCRL, RESET and MODE.
The ED510 displays current burner status, first out annunciation in the event of a lockout condition,
historical burner information, detailed lockout information of the last six (6) lockout conditions and
programmer configuration information. Through the display the ability to program the unit address
for communications, as well as resetting the stored information (cycles, hours, and lockouts) to zero
is provided.
Depending on the information being displayed, data is displayed on the ED510 screen in the follow-
ing locations:
At any time the MicroM is powered, the SCRL key is used to scroll through and display the total
number burner hours, burner cycles, burner lockouts and system hours on the bottom line of the
ED510 display. The top line will continue to show the current run mode of the control (e.g. PURGE,
AUTO, etc.) Following the historical information, the SCRL key will display three (3) sub-menus
providing the following information and/or functions:
Lockout History (with burner cycle and burner hour time stamp).
Program Setup (to display programmer type, purge timing, switch configuration, etc.)
System Information (values of average pilot and main flame signal, and reset burner his-
tory).
The system sub-menus require the MODE key to gain access to the information associated with each
sub-menu. An arrow is displayed in the lower right hand corner of the display to indicate a system
sub-menu is available. Once within the sub-menu, pressing the SCRL key displays the next item
within the sub-menu, and pressing the MODE key will exit the sub-menu and return the display to
the top of the main menu.
SCRL RESET
MODE
PURGE 00:05
STARTING BURNER
OPERATING STATUS
(Standby, Purge, PTFI,
Auto, etc.)
ADDITIONAL INFORMATION
(Flame Signal Strength, Cause of current Lockout, etc.) OR
BURNER HISTORY (SCRL key required)
(Burner Cycles, Burner Lockouts, etc.) OR
SUB-MENU HEADINGS (SCRL and MODE keys required)
(Lockout History, Program Setup, etc.
ON OPERATING STATUS
TIMING
(During Purge or PTFI) OR
FLAME SIGNAL STRENGTH
(During PTFI, MTFI, or Auto)
ARROW displayed when
MODE key is required to
access sub-menus
(Lockout, History, Program
Setup, etc.)
FIREYE
SMDK-1
3 Manchester Road APRIL 11, 2013
Derry, New Hampshire 03038 USA Supersedes January 18, 2006