Product Overview

1
®
DESCRIPTION
The Fireye MP100, MP100E, MP101, MP102, MP102E, MP230, MP230H, MP560, MP561 and
MP562 Programmer Modules are used with the Fireye Modular M-Series II control. The operational
characteristics of the control are determined by the selection of the programmer module (e.g. re-igni-
tion, 2-stage capability, pilot cutoff, etc.). The programmer module incorporates a plug-in design for
easy installation.
Some programmer modules (MP230, MP230H, MP560, MP561, and MP562) are equipped with a
series of dipswitches to select Purge Timing. Pilot Trial for Ignition (PTFI) Timing, and Recycle or
Non-Recycle operation. LED indicator lights are on all programmer modules, indicating the operat-
ing status of the control. A “check-run” switch is provided on the MP560, MP561 and MP562 pro-
grammer modules to assist in testing size and stabilization of the pilot.
Flame Failure Response Time (FFRT) is determined by the selection of the amplifier module. Test
jacks are also provided on the flame amplifier module to permit flame signal measurement during
operation. For proper and safe application of this product, you must refer to Fireye bulletin C-4000
or C-4000E for a detailed description of the various programmer modules, including installation
instructions, amplifier selection, operating sequences for each programmer module, etc.
WARNING: Selection of this control for a particular application should be made by a com-
petent professional, licensed by a state or other government agency. Inappropriate application
of this product could result in an unsafe condition hazardous to life and property. Installation
should not be considered complete until pilot turndown and other appropriate performance
tests have been successfully completed.
PROGRAMMER MODULE SELECTION
Part Number DESCRIPTION
MP100/MP100E Relight operation.
MP101 Same as MP100, except will ignore flame signal in off cycle.
MP102/MP102E Operates like the MP100, except the standing pilot and relight features are eliminated. Ignition safety time is
5 seconds. Control will lockout on flame failure.
MP230 Selectable purge timing, trial-for-ignition timing, and recycle/non-recycle operation.
MP230H Selectable purge timing, trial-for-ignition timing, pilot stabilizing period, and recycle/non-recycle operation.
10 second main flame trial-for-ignition. For use with two-stage burners.
MP560 Selectable purge timing, pilot-trial-for-ignition timing, pilot stabilizing period, and recycle/non-recycle operation.
10 second main flame trial-for-ignition, check-run switch.
MP561 Selectable purge timing, pilot-trial-for-ignition timing, and recycle/non-recycle operation. 10 second main flame trial-for-ignition,
check-run switch.
MP562 Same as MP560, with lockout on loss of air flow. Non-recycle operation.
Programmers with the suffix “E” (e.g. MP100E) are for use with the MC230 and MC230R chassis only.
MP100, MP100E, MP101,
MP102, MP102E, MP230,
MP230H, MP560, MP561,
and MP562
PROGRAMMER MODULES FOR USE WITH THE
FIREYE MODULAR M-SERIES II CONTROL
C-4001
MARCH 2005