Product Overview

2
®
WARNING: Remove power from the control and remove the control from its wiring base
before proceeding.
INSTALLATION
The Programmer Modules are used with the Fireye modu-
lar M-Series II Chassis (P/N MC120, MC120E, MC120P,
MC120R and MC120RE for 120VAC, MC230 and
MC230R for 240 VAC). They are installed in the chassis
by grabbing hold of the programmer module by the ridged
finger grips on the side on the module, aligning the module
with the guide slots on the opening farthest from the trans-
former, and inserting the module into the pin connectors.
The programmer modules are designed to fit in the proper
slot only. DO NOT FORCE THEM. Replaceable Fuse:
The programmer modules are designed with a field-
replaceable fuse.
The fuse is located on the printed circuit board near the
connectors. The fuse will open as a result of an overload
condition on terminals 3, 4, or 5. In the event the fuse
opens, remove the fuse (using a small screwdriver) and install a Fireye replacement fuse (P/N 23-176) or equiv-
alent 2AG, 8 amp fuse (e.g. Littlefuse #225008) In programmers used with the MC230 and MC230R, use
replacement fuse
P/.N 23-183 or equivalent (3.5 amp, 2AG, SLO-BLO) Littlefuse #22903.5.
APPROVALS
Underwriters Laboratories Inc. Listed Guide MCCZ — File MP1537
Underwriters Laboratories Inc. Listed MCCZ File MP1537
Canadian Standards Association: Guide 300-1-0.2 Class 2642 Oil File LR 7989
Guide 140-A-2 Class 2632 Gas File LR7989
Factory Mutual
EN230 EN298
Approvals do not apply to MC230 and MC230R Chassis and associated programmers.