Product Overview

INSTALLATION
The Programmer Modules are used with the
Fireye modular MicroM Chassis
(P/N MEC120, MEC120RC, MEC120R,
MEC120D, MEC120RD and MEC120C for
120VAC and MEC230 for 230 VAC). They
are installed in the chassis by grabbing hold
of the programmer module by the ridged fin-
ger grips on the side on the module, aligning
the module with the guide slots on the open-
ing farthest from the transformer, and insert-
ing the module into the pin connectors.
PROGRAMMER DIPSWITCH SETTINGS
NOTE: The dipswitch settings become permanently stored within the programmers eeprom mem-
ory after 8 hours of continuous electrical operation. This allows sufficient opportunity to make
the appropriate selection, test and checkout the system. Once stored, the settings cannot be altered.
The MEP500 series programmers have a series of 6 dipswitches which allow the user to program the
purge timing, trial for ignition timing, enable post purge, enable proof of air flow open proven and
start and select recycle/non-recycle operation.
MicroM Programmer Dip Switch Configuration
Note: C refers to switch closed position, and closed position is when the switch is toward the printed circuit
board. O refers to open switch position or when the switch is moved away from the printed circuit board.
SWITCH FUNCTION
654321
CC
7 PURGE*
TIME
SECONDS
CO
30
OC
60
OO
90
C
DISABLED POST
PURGEO
15 SECONDS
C
5 PTFI
TIMEO
10
C
DISABLE PROVE
AIR FLOWO
ENABLE
C
RECYCLE
O
NON-RECYCLE
The programmer modules
are designed to fit into the
proper slot only.
DO NOT
FORCE THEM
FIREYE MP-5501
3 Manchester Road APRIL 3, 2013
Derry, New Hampshire 03038 USA Supersedes November 19, 2007
www.fireye.com
* The MEP561 Programmer
module has selectable purge
timings of 7, 10, 15 and 30
seconds.
* The MEP564 Programmer
module has selectable purge
timings of 7, 30, 60 and 240
seconds.