42 • FIREYE PRIMELINE PRODUCTS
FLAME SCANNERS AND APPLICATIONS
The following Fireye flame scanners are used in conjunction with the appropriate Fireye flame safeguard controls to provide reliable flame
detection on a variety of burner applications and fuel types.
UVIA Bulletin SC-102
Ultraviolet miniature non self-checking scanners. The UV1A is suitable
for fuel gases and no. 2 oil. Non-replaceable tube. Mounting collar 1/2"
NPT. Available with 3 ft (UV1A3), 6 ft. (UV1A6), or 50 ft. (UV1A50) of
tray-rated cable. Explosion proof housings are available.
UV90 Bulletin SC-102
Ultraviolet miniature non self-checking scanner suitable for frontal or
side (90°) viewing. Complete with mounting fixture. Available with 3 ft
(UV90-3), 6 ft. (UV90-6), or 9 ft. (UV90-9) of flexible conduit.
UV2 Bulletin SC-103
Ultraviolet miniature non self-checking scanner. Similar in function to
the UV1A3 but with a smaller mounting collar (3/8"). Non-replaceable
tube.
UV8A Bulletin SC-102
A 90 version of the UV1A6, but with unshielded leads and 0.70"
diameter collar to be used with a 1/2" E.M.T rain tight fitting (not fur-
nished). The mounting collar is 1/2" NPT. Must be installed with metal
shielding over the scanner leads.
45UV5-1005, -1006, -1007, -1009 Bulletin SC-103
Self-checking ultraviolet scanner is for continuously fired applications
where recycling is infrequent or absent. The self-checking circuit
checks the electronics and the UV tube for proper operation every
four seconds during the firing period. Suitable for fuel gases and oil.
Replaceable UV tube and (4-314-1) shutter mechanism (61-2914-1).
Mounting 1" NPT or BSP pipe thread with 6 ft. (1.8m) lead wires.
Must be installed with metal shielding over the scanner leads. Explo-
sion-proof housings are available for models 45UV5-1005, 45UV5-
1007, and 45UV5-1009.