FIREYE PRIMELINE PRODUCTS • 33
PART NUMBER Programmers for use with MEC320 / MEC480 Chassis
MEP300 Relight operation on main flame fail, lockout on PTFI and MTFI flame fail, 10 sec PTFI (fixed),
5 sec pilot proving, 5 sec MTFI.
MEP304 5 sec purge, 10 sec PTFI (fixed), 5 sec pilot proving, 10 sec MTFI,
interrupted pilot, interrupted ignition, non-recycle on flame fail.
MEP397 15 sec purge, provides interrupted ignition, interrupted pilot, non re-cycle on flame fail.
MEP696 Provides selectable PTFI, selectable baud rate, and selectable recycle / non-recycle operation.
For use with MEC320TS chassis only.
MEP697 Selectable TFI timing, purge timing, post purge, prove open at start, and recycle / non-recycle on flame fail. Includes 5 sec pilot
proving, early spark termination, 5 sec MTFI, and interrupted pilot.
PART NUMBER MicroM Amplifier Models (common for all controls)
MEUV1 UV amplifier, 0.8 second FFRT, uses UV1A, UV2, UV8A and 45UV3-1050 scanners
MEUV4 UV amplifier, 3 second FFRT, uses UV1A, UV2, UV8A and 45UV3-1050 scanners
MEUVS1 UV Self-Check amplifier, 0.8 second FFRT, uses 45UV5-1007, -1008, -1009 scanners
MEUVS4 UV Self-Check amplifier, 3 second FFRT, uses 45UV5-1007, -1008, -1009 scanners
MERT1 Flame Rod / Photocell amplifier, 0.8 second FFRT, uses 69ND1 or 45CM1
MERT4 Flame Rod / Photocell amplifier, 3 second FFRT, uses 69ND1 or 45CM1
MEIR1 Infrared amplifier, 0.8 second FFRT, uses 48PT2 scanner
MEIR4 Infrared amplifier, 3 second FFRT, uses 48PT2 scanner
MECD1 Cadmium sulfide amplifier, 0.8 second FFRT, uses CS1A5 scanner
MECD4 Cadmium sulfide amplifier, 3 second FFRT, uses CS1A5 scanner
PART NUMBER Optional Plug-In Board Module (common for all controls)
MED1 Standard local reset switch
MED2 Same as MED1 with display output
MED3 Same as MED1 with remote reset
MED4 Same as MED1 with display output and remote reset
MED5 Same as MED1 with display output and communications
MED6 Same as MED1 with display output, remote reset and communications
MED7 Same as MED1 with communications
PART NUMBER Wiring Base (Common for All Controls)
61-3060 Closed wiring base, surface mounting
61-5042 Open wiring base, cabinet mounting
PART NUMBER Programmers and Flame Amplifiers for use with Integrated Flame Scanners
MEP237 Programmer, Selectable recycle/non-recycle function, TFI timing, purge timing, post purge, prove open at start. Provides 0.30
second flame failure response time, for use with Phoenix and InSight flame scanner and MEDC2 amplifier.
MEDC2 Amplifier for use with dry contact input from Phoenix and InSight flame scanner, 0.30 sec FFRT.
Use with MEP237 and 85UVF4-1QDWR, 85IRF4-1QDWR, or InSight scanner (with 59- 497-020WR cable).