Brochure

30 • FIREYE PRIMELINE PRODUCTS
DIRECT REPLACEMENT UPGRADES
No wiring changes necessary (see Notes)
Use existing wiring base and flame scanner.
C-Series or D-Series to E110 Flame-Monitor
D-Series to Flame-Monitor
C-SERIES MODEL D-SERIES FLAME-MONITOR
25CU6-5065 70D10, 71D60
72DUV1
E110, ED510,
EP160, EUV1
25CU6-5066 70D20, 71D60
72DUV1
E110, ED510,
EP260, EUV1
26CF6-5022 70D10, 71D60
72D1R1
E110, ED510,
EP160, E1R1
26CF6-5023 70D20, 71D60
72D1R1
E110, ED510,
EP260, E1R1
25CU6-5062* 70D30, 71D80
72DUV1
E110, ED510,
EP380, EUV1
25CU6-5063
* 70D30, 71D90
72DUV1
E110, ED510,
EP390, EUV1
26CF6-5020 70D30, 71D80
72D1R1
E110, ED510,
EP380, E1R1
26CF6-5021 70D30, 71D90
72D1R1
E110, ED510,
EP390, E1R1
24CJ5-5010 70D30, 71D80
72DRT1
E110, ED510,
EP380, ERT1
24CJ5-5011 70D30, 71D90
72DRT1
E110, ED510,
EP390, ERT1
D-SERIES CHASSIS AND
PROGRAMMER
E-SERIES
PROIGRAMMER
70D10 and 71D60 EP160
All Flame-Monitor controls
require an E110 chassis and
ED510 display
module.
70D10 and 71D61 EP161
70D10 and 71D70 EP170
70D20 and 71D60 EP260
70D20 and 71D61 EP261
70D20 and 71D70 EP270
70D30 and 71D80 EP380
70D30 and 71D81 EP381
70D30 and 71D90 EP390
D-SERIES AMPLIFIER E-SERIES AMPLIFIER USE WITH FLAME SCANNERS
72DUV1 EUV1 UV1A, UV2, UV8A, UV90, 45UV3-
1050
72D1R1 E1R1 48PT2
72DRT1 ERT1* 45CM1, 69ND1
72DUVS4 EUVS4 45UV5-1007, -1008, -1009
Refer to Bulletin E-1101 for proper
installation, grounding, operational and
safety checkout procedures. Perform
safety checks of the entire system prior
to allowing fuel entry to boiler.
*Ensure S2 is connected to earth
ground when using ERT1.
CAUTION
Notes:
L1-13, 13-3 circuits: Some C-Series and
D-Series controls were installed on a burner
that did not have a fuel valve end switch termi-
nal (13 – 3) and the operating control was
wired between L1 and 3. When upgrading to a
Flame-Monitor on these installations, after ver-
ifying a fuel valve end switch is not installed
(e.g., no wire on terminal 13), jumper terminal
13 to 3.
Early Spark Termination (Terminal X): On the
non-modulating C-Series and D-Series
(70D30) controls, terminal X would provide a 5
second pilot trial for ignition (PTFI). If terminal
X is required, terminal 5 must be jumpered to
terminal 10 when using the EP380, EP381, or
EP390 programmers.
*No terminal 10 (open damper purge) on D-
Series of Flame-Monitor. Add timer if terminal
10 is used for open damper.