Brochure
14 • FIREYE PRIMELINE PRODUCTS
YB110/YB230 FIREYE BURNERLOGIX™ CONTROL Bulletin BL-1001
The Fireye
®
BurnerLogix™ System is a microprocessor based burner management
control system designed to provide the proper burner sequencing, ignition and flame
monitoring protection on automatically ignited oil, gas, and combination fuel burners.
In conjunction with limit and operating controls, it programs the burner/blower motor,
ignition and fuel valves to provide for proper and safe burner operation. Through
SMART LED’S, the control provides current operating status and lockout information
in the event of a safety shutdown. Optional VFD and LCD displays are available that
may be either plugged in or mounted remotely to give full language descriptors of cur-
rent status and diagnostic lockout information.
A complete BurnerLogix system includes the YB110 (YB230) chassis equipped with
the type of flame amplifier required for the application, appropriate flame detector,
plug-in programmer module, wiring base and optional alpha-numeric display. Inter-
changeable programmer modules allow for complete versatility in selection of func-
tion, timing and flame failure response times.
The optional alpha-numeric display is made up of 2 lines by 16 characters per line and is available in either vacuum fluores-
cent or liquid crystal formats. Both displays contain a fully functional keypad allowing the user to easily scroll through the var-
ious menus to view the current operating status, review programmer configuration, and lockout history. An advantage of the
BurnerLogix control family is the ability to set many of the operating parameters associated with proper and reliable burner
operation allowing inventory of various programmer types to be kept to a minimum.
Interchangeable YP programmer modules allow for complete versatility in selection of control function, timing, and flame
scanning means. Functions such as pre-purge time, recycling or non-recycling interlocks, high fire proving interlock and trial
for ignition timing of the pilot and main flame are determined by the programmer module. The BurnerLogix system can be
used with ultra-violet, auto-check infrared, flame rod, self-check ultra-violet flame scanners or direct coupled integrated scan-
ners by choosing the proper chassis/flame amplifier module.
Wiring bases for the BurnerLogix control are available pre-wired with 4 foot lead wires color coded and marked for easy instal-
lation or with an integral terminal block capable of a accepting up to 2 X 14 AWG wires. The wiring base terminal block is avail-
able with knockouts for conduit or open ended for cabinet mounting. The pigtail wiring base is 4" X 5" and the terminal block
wiring base is 4" X 7".
Additional functions of the BurnerLogix system include:
• A consistent flame signal read-out via display module or 4-20 mA output.
• Read-out of main fuel operational hours and complete cycles via display module.
• Modbus communications via RS485 multi-drop link.
• Proof of fuel valve closure during off cycle.
• Burn-in time of program parameters occurs after 8 hours of main valve on time.
• A run/check switch which allows the operator to stop the program sequence in any of four
different positions (Purge, PTFI, MTFI or Auto).
• Remote Display mounting with NEMA 4 protection.
• Remote Reset.
• Revert to pilot can increase burner turn down.
BurnerLogix Chassis/Flame Amplifier Module
PART NUMBER DESCRIPTION
YB110UV
120 VAC input with UV non self-check amplifier
YB110UVSC
120 VAC input with UV self-check amplifier