Brochure

FIREYE PRIMELINE PRODUCTS • 13
E300 EXPANSION MODULE Bulletin E-3001
The Fireye E300 Expansion Module provides increased interlock supervision capability of the
Flame-Monitor control system. By wiring any of 16 interlock switches into the Expansion Mod-
ule (three additional recycling interlocks and 13 additional running safety interlocks), the
Flame-Monitor will automatically act as a “first out” annunciator for these interlocks. The user
can select the lockout message associated with each set of terminals of the E300 from a
library of messages using the ED510 display module. The user can also customize the lockout
alarm messages (up to 40 characters in length) by using an IBM compatible PC, E300 soft-
ware (contact Fireye), EC485 converter, and ED512 cable. The E300 Expansion Module con-
nects to the EB700 Chassis with an E350 ribbon cable. The Expansion Module does not
interfere with the normal operation of the Flame-Monitor system. It expands the diagnostic
capability of the control, identifying the specific limit in the operating control circuit (LI-13) or
running safety interlock circuit (3-P) which caused the burner shutdown or lockout, reducing
troubleshooting time and expense.
DIMENSIONS
PARTIAL LIST OF SELECTABLE MESSAGES PROVIDED USING ED510 DISPLAY MODULE
E340 OP CNTL OPEN HIGH OIL PRESSURE LOW OIL TEMPERATURE E340 SAFETY INTLK OPEN
LOW GAS PRESSURE LOW WATER HIGH OIL TEMPERATURE F.D.FAN INTLK
HIGH GAS PRESSURE HIGH WATER HIGH PRESSURE I.D. FAN INTLK
HIGH STACK TEMPERATURE LOW ATOMIZING MEDIA HIGH TEMPERATURE BLOWER MOTOR INTLK
LOW OIL PRESSURE HIGH STACK TEMPERATURE AIR FLOW OPEN OIL GUN END SWITCH OPEN
PART NUMBER DESCRIPTION
E300 120 VAC Expansion Module for Flame-Monitor
E350-3 Expansion Module cable, 3 ft.
E350-6 Expansion Module cable, 6 ft.
60-1950 Wiring Base for E300
EC485 RS232/RS485 converter for programming custom messages
UC485 USB / RS485 converter for programming custom messages
ED512-2 RJ12 connector cable - 2 ft. for programming custom messages
Contact Fireye for software for programming customized messages.
WIRING BASE
MOUNTING HOLES
7 1/4
(184.2)
6
(152.4)
3 1/2
(89)
1/2” KNOCKOUT
CONTROL WITH COVER AND
P/N 60-1950 WIRING BASE
4 7/8
(123.8
5 11/
16
2 7/16
(61.9)
5 1/4
(133)
7
(177.8
11/16
(17.4)
3/4
(44.4)
25/32
(19.8)
1/4
TYP
(6.35)
390
TYP
KNOCKOUTS
FOR
1 1/16
(27)
1 3/16