Brochure
12 • FIREYE PRIMELINE PRODUCTS
FLAME AMPLIFIER MODULES Bulletin EAMP-1
The Fireye Flame Amplifier Modules are used in conjunction with the appropriate
flame scanner to provide flame scanning capability in the FLAME-MONITOR sys-
tem. Fireye offers ultraviolet amplifiers (EUV1), self-check ultraviolet amplifiers
(EUVS4), flame rectification amplifiers for use with flame rods and photocells
(ERT1), and auto-check infrared amplifiers: E1R1 (standard model), E1R2 (high
sensitivity - consult factory before use), and E1R3 (for solid fuels).
Self-checking ultra-violet scanners and amplifiers should be used in applications
where burner firing operation is continuous or where the burner is on for long
periods of time (e.g. 24 hours) without cycling.
The flame amplifier must be used with the appropriate flame scanners as shown
below.
When replacing any flame scanner or amplifier, the burner should be cycled on
and off several times to ensure proper operation.
PART NUMBER DESCRIPTION
EUV1 UV Amplifier for UV1A, UV8A, UV2, 45UV3, UV90
E1R1 Infrared Amplifier for 48PT2 Scanner
E1R2 Infrared Amplifier (High Sensitivity) for 48PT2 Scanner. Consult factory before use.
E1R3 Infrared Amplifier (for solid fuels) for 48PT2 Scanner.
EUVS4 Self-Check UV Amplifier for 45UV5-1007, -1008, -1009, -1005
ERT1 Rectification Amplifier for 45CM1, 69ND1
EDC1 Amplifier for use with the EP178/EP378 and one or two 85UVF4-1QDWR or InSight flame scanners
(with 59-497-020WR cable).
EDC2 Amplifier for use with the EP178/EP378 and one or two 85UVF4-1QDWR or InSight flame scanners (with 59-497-
020WR cable) to monitor pilot and main. Scanners automatically switched at appropriate time.