Brochure

8 • FIREYE PRIMELINE PRODUCTS
FLAME-MONITOR™ CONTROL Bulletin E-1101
The Flame-Monitor Series provides the proper burner sequencing, ignition and
flame monitoring protection on automatically ignited oil, gas and combination fuel
burners. On a safety shutdown, the display module will advise the operator that the
control is in “Lockout” and indicate the cause as well as the position in the operat-
ing sequence that it occurred.
Interchangeable programmer and flame amplifier modules allow complete versa-
tility in selecting control function. The Flame-Monitor control uses the same wiring
base as the Fireye D-Series and C-Series Controls and is directly interchangeable
with most models without rewiring.
The Flame-Monitor control can be used with ultraviolet, AUTOCHECK
®
infrared,
photocell, flame rod or self-check ultraviolet flame scanners by choosing the proper
amplifier module. Special features include: remote reset, remote display, expanded
annunciation of safety lockouts, programmability of safety interlock messages, and
remote data communications capability. A 220 volt version of the E110 control is
also available without any agency approvals. (P/N E120).
The complete FLAME-MONITOR control consists of:
DIMENSIONS
Part Number Description
E100 OBSOLETE - Replace with E110. Display required.
E110 Standard unit consisting of one each EB700, 48-1836, and EC600. Display ordered separately. 120VAC.
E120 Standard unit, consisting of one each EB701, 48-1836, and EC600. 220VAC operation. No agency approvals.
EB700 Replacement chassis only for E110 and E100.
EC600 Replacement dust cover for E110 and E100.
48-1805 Mounting screw for E100, E200, E201,E340
48-1836 Mounting screw for E110, E120, E210, E211
60-1386-2 Wiring Base - Surface Mount
60-1466-2 Wiring Base - Cabinet Mount
14-64 Noise line filter for E100/E110
E110 Chassis
ED510 Display Module
EP Programmer or EPD Programmers
(EPD programmers do not require ED510 display)
•Amplifier
Scanner
Wiring Base
7 9/32
(185)
6
(152)
1 7/8
(48)
5 3/4
(146)
1/2” KNOCKOUT
CONTROL WITH COVER
AND WIRING BASE
4 7/8
(123.8)
5 11/16
(144.5)
2 7/16
(61.9)
5 1/4
(133)
7
(177.8)
11/16
(17.4)
3/4
(44.4)
25/32
(19.8)
1/4
TYP
(6.35)
390
TYP
(9.9)
KNOCKOUTS FOR
1/2” CONDUIT (7)
1 1/16
(27)
1 3/16
(30.2)
WIRING BASE
MOUNTING HOLES
3 5/8 (92)