Brochure

34 • FIREYE PRIMELINE PRODUCTS
M-SERIES II Bulletins C -4000, C -4001, C -4002
Fireye modular M-Series II Flame Safeguard controls are compact, mod-
ular burner management systems. They provide automatic ignition and
continuous flame monitoring for commercial-sized heating and process
burners using gas and/or light oil fuels.
Flame sensing is accomplished by miniature UV scanners or Flame Rod/
Photocell detectors and plug-in amplifier and programmer modules con-
nected into a standard chassis and wiring base. Interchangeable pro-
grammer and amplifier modules allow complete versatility when
selecting control function, timing, and flame scanning means. Functions
such as relight, two stage capability, purge timing, and pilot cutoff are
determined by the programmer module. Type of flame scanner (UV,
flame rod, or photocell) and Flame Failure Response Time (FFRT) are
determined by the amplifier module. Some programmer modules have
dipswitches for selecting purge timing, pilot trial-for-ignition (PTFI) tim-
ing, and recycle or non-recycle operation. LED indicator lights on all pro-
grammer modules indicate operating status of the control.
In the event of ignition failure, or after a safety shutdown, the unit locks out, activating an alarm circuit. Manual reset is required. Remote
reset (via remote push-button or power interruption) is available on the MC120R chassis. Post purge is available on the MC120P chassis.
Test jacks permit flame signal measurement during operation. A “run-check” switch on the MP560, MP561, MP562 programmer module
assists in testing size, position, and pilot stabilization.
Modular M-Series II controls incorporate a safety checking circuit that is operative on each start. If flame (real or simulated) is detected
before a start or during the purge, the fuel valves will not be energized, and the unit will lock out.
DIMENSIONS
CHASSIS (shown with Programmer Module)
5 3/16
5 3/16
MOUNTING BASE
5 5/16
4
4
1/2
1/2
3/16” DIA. MOUNTING
HOLES (4)
KNOCKOUTS
(12)
FOR 1/2”