Brochure

32 • FIREYE PRIMELINE PRODUCTS
PART NUMBER MicroM Programmer Models, for use with MEC120/MEC230 chassis
MEP100 Relight operation, 10 sec. PTFI
MEP101 Relight operation, allow flame signal during “off cycle”
MEP102 Non-recycle on flame fail, 5 second PTFI
MEP103 Fixed 10 second PTFI, 10 second MTFI, re-try once on pilot failure, post purge
MEP104 Non-recycle on flame fail, 10 second PTFI
MEP105 Non-recycle on flame fail, lockout on air flow open with flame present, 10 FTFI.
MEP106 Relight operation, 12 sec purge, 10 sec PTFI, reset lockout on line power interruption.
MEP107 5 sec purge, 10 second PTFI, 5 minute delay following flame failure. For natural draft atmospheric gas burners
MEP108 Non-recycle operation, 0 sec purge, 15 second PTFI, 10 sec-ond post purge, no FM Approval.
MEP109 Immediate ignition and pilot after limits are closed, 10 sec PTFI (fixed), 10 sec MTFI, intermittent pilot, non-recycle on flame fail.
MEP100P Relight operation, 10 sec PTFI, 15 second post purge.
MEP130 Relight operation, 30 sec PTFI, no agency approvals
MEP141 30 sec purge, 5 sec PTFI, 15 sec post purge, Prove air at start, 8 sec pilot stabilization, non-recycle on flame fail.
MEP149 30 sec purge, 5 sec PTFI, 90 sec post purge, prove air at start, 8 sec pilot stabilization, non-recycle on flame fail.
MEP230 Selectable purge timing, PTFI timing, recycle/non-recycle, post purge, prove air open at start
MEP230H Same as MEP230 with 8 second pilot stabilization
MEP235 Same as MEP230 with lockout on air flow open 10 seconds after the start of a cycle, selectable recycle/nonrecycle lockout on air
flow open after flame is proven and dedicated lockout after loss of flame.
MEP236 Same as MEP230 with additional 6 second igniter on time with main fuel. To be used with intermittent pilot only.
MEP238 Selectable recycle/non-recycle function, TFI timing, purge timing, post purge, prove open at start. Ignition de-energized 3 seconds
after pilot detected. Provides 8 second pilot stabilization period.
MEP290 Same as MEP230 except selectable post purge is 0 or 90 seconds.
MEP437 Valve proof of closure, selectable purge, PTFI timing, intermittent or interrupted, recycle / non-recycle operation, reset by power
interruption of manual reset.
MEP536 Same as MEP236, 10 second trial for ignition, run-check switch, will not lockout on air flow open during purge.
MEP537 Selectable purge, PTFI, post purge, prove open at start, recycle/non-recycle (with one recycle on flame fail), 10 sec MTFI.
MEP560 Same as MEP230H, 10 second main trial for ignition, run-check switch
MEP561 Same as MEP560 without pilot stabilization
MEP562 Same as MEP560, lockout on loss of air flow, non-recycle operation only
MEP564 Same as MEP560 except purge timings are 7 30, 60, and 240 (4 minutes) seconds.
PART NUMBER MicroM Series MEC320 Chassis for use with MEP300 and 600 Series Programmers
MEC320 MicroM chassis with local reset; 120 VAC, 50/60 Hz, provides independent relay outputs on terminals 3 and 4.
For use with MEP300 and MEP600 series programmers.
MEC320R MicroM MEC320 chassis with remote reset. For use with MEP300 and 600 series programmers.
MEC320D MicroM MEC320 chassis with alpha-numeric display interface to ED510. For use with MEP300 and 600 series programmers.
MEC320C MicroM MEC320 chassis with interface to E500 Communication Interface and Modbus capability.
For use with MEP300 and 600 series programmers.
MEC320RC MicroM MEC320 chassis with remote reset capability, interface to ED510, interface to E500 Comm. Interface, and
Modbus capability. For use with MEP300 and 600 series programmers.
MEC320RD MicroM MEC320 chassis with remote reset capability and interface to ED510.
For use with MEP300 and 600 series programmers.
MEC320TS MicroM MEC320 chassis with remote communications and independent relay output.
For use with MEP696 programmer only.
MEC480 MicroM chassis with local reset; 230 VAC, 50/60 Hz, pro-vides independent relay outputs on terminals 3 and 4.
For use with MEP300 and 600 series programmers.