FIREYE PRIMELINE PRODUCTS • 17
Additional functions of the BurnerLogix Z System include:
• A non-volatile memory which allows the control to remember its history and present position even when power is
interrupted.
• A consistent flame signal read-out via display module or 4-20 mA output.
• Read-out of main fuel operational hours and complete cycles via display module.
• Modbus communications via RS485 multi-drop link.
• Proof of fuel valve closure during off cycle.
• Burn-in time of program parameters occurs after 8 hours of main valve on time.
• A run/check switch which allows the operator to stop the program sequence in any of four different positions
(Purge, PTFI, MTFI or Auto).
• Remote Display mounting with NEMA 4 protection.
• Remote Reset
• Keypad selectable language readout.
• Revert to pilot can increase burner turn down.
BurnerLogix Z Chassis/Flame Amplifier Module
BurnerLogix Z Programmer Modules
BurnerLogix Z Displays
BurnerLogix Z Wiring Bases
BurnerLogix Z Accessories
PART NUMBER DESCRIPTION
ZB110UV
120 VAC input with UV non self-check amplifier
ZB110UVSC
120 VAC input with UV self-check amplifier
ZB110IR
120 VAC input with IR auto-check amplifier
ZB110IR2
120 VAC input with IR auto-check amplifier (special application only - consult factory)
ZB230UV
230 VAC input with UV non self-check amplifier
ZB230UVSC
230 VAC input with UV self-check amplifier
ZB230IR
230 VAC input with IR auto-check amplifier
PART NUMBER DESCRIPTION
YP100
Keypad selectable parameters, non-recycle operation, modulation, open damper proving, 4 second FFRT
YP102
Keypad selectable parameters, non-recycle operation, modulation, open damper proving, 2 second FFRT
YP113
Keypad selectable parameters, non-recycle operation, modulation, open damper proving, 1 second FFRT
YP118
Keypad selectable parameters, non-recycle operation, modulation, open damper proving, indefinite pilot
hold, revert to pilot from auto, 1 second FFRT
YP138
Keypad selectable parameters, non-recycle operation, modulation, open damper proving, indefinite pilot
hold, revert to pilot from auto, 4 second FFRT
PART NUMBER DESCRIPTION
BLV512
Display, 2 line X 16 characters, VFD, with cable, NEMA 4
BLL510
Display, 2 line X 16 characters, LCD, with cable, NEMA 4
PART NUMBER DESCRIPTION
60-2850-1
Pigtail wires, 4 foot long, 4"W x 5"H
60-2852-1
Closed base with terminal block and knockouts, 4"W x 7"H
60-2854-1
Open base with terminal block. 4"W x 7"H
PART NUMBER DESCRIPTION
129-178-4
Kit, remote mounting, BurnerLogix display, 4 ft. cable, provides NEMA 4 protection
129-178-8
Kit, remote mounting, BurnerLogix display, 8 ft. cable, provides NEMA 4 protection
BLD500
Blank display module, included with ZB module
IT1000
Alarm annunciation system using wireless technology
PPC6000
Parallel Positioning System
61-5745-3
Shutter drive assembly for redundant self-check 45UV5-1005 scanners